Communication with Other Devices<br />

A new OPC .Net Client worksheet is displayed:<br />

OPC .Net Client worksheet<br />

2. In the Description box, type a description of the worksheet. This is for documentation purposes only and<br />

does not affect the execution of the worksheet.<br />

3. In the Connection list, select the OPC Server connection that you configured earlier.<br />

4. For more connection options, click Advanced.<br />

The Advanced dialog is displayed:<br />

Review the options and configure as needed:<br />

Area / Element<br />

Read actions<br />

Enable subscription<br />

Description<br />

When this value is TRUE (non-zero), the client will constantly request updates from the server.<br />

Note: This is enabled by default. If it is disabled, then you must use a read trigger (see<br />

below).<br />

Maximum group size<br />

Synchronous read<br />

trigger<br />

The maximum number of tag reads that may be performed in a single read operation.<br />

For example, if you have 1000 items/rows configured in the worksheet and Maximum group size is set<br />

to 100, then 10 read operations will be performed during each scan of the worksheet.<br />

When the value of this tag/expression changes, the worksheet is scanned and all tag values are read<br />

from the server. The project waits for the scan to complete before continuing.<br />