Operation<br />

No.<br />

Abbreviation<br />

Meaning<br />

Displayable<br />

values<br />

Unit<br />

Rest<br />

poss.<br />

31 VENT1 Number of cycles pre--<strong>control</strong>valve 1 0to4.29E9 --<br />

32 VENT2 Number of cycles pre--<strong>control</strong>valve 2 0to4.29E9 --<br />

33 STORE Store current values as ”last maintenance”<br />

-- --<br />

(press increment key for 5 s)<br />

34 PRUP Prediction up 1to40 --<br />

35 PRDN Prediction down 1to40 --<br />

36 WT00 Number of operating hours in distance class WT00 0to4.29E9 Hours x<br />

37 WT05 Number of operating hours in distance class WT05 0to4.29E9 Hours x<br />

38 WT10 Number of operating hours in distance class WT10 0to4.29E9 Hours x<br />

39 WT30 Number of operating hours in distance class WT30 0to4.29E9 Hours x<br />

40 WT50 Number of operating hours in distance class WT50 0to4.29E9 Hours x<br />

41 WT70 Number of operating hours in distance class WT70 0to4.29E9 Hours x<br />

42 WT90 Number of operating hours in distance class WT90 0to4.29E9 Hours x<br />

43 WT95 Number of operating hours in distance class WT95 0to4.29E9 Hours x<br />

44 mA Current setpoint 0.0 to 20.0 mA<br />

Table 4-1<br />

Over<strong>view</strong> diagnostic values<br />

4.5.2 Meaning of the diagnostic values<br />

1 STRKS<br />

Number of strokes<br />

The actuator movements during operation are totaled and can be read<br />

here as number of strokes. Unit: 100% stokes The value is written every<br />

15 minutes in a non--volatile memory. It can be reset to zero with<br />

the increment key .<br />

2 CHDIR<br />

Number of direction changes<br />

Every change in direction leaving the dead zone is noted in the<br />

<strong>control</strong>ler and added to the number of changes of direction.<br />

The value is written every 15 minutes in a non--volatile memory. It can<br />

be reset to zero with the increment key .<br />

3 CNT<br />

Fault counter<br />

Every fault is noted in the <strong>control</strong>ler and added to the number of fault<br />

messages. The counter can be reset to zero with the increment key .<br />

SIPART PS2 Manual<br />

A5E00074631-03<br />

99