Technical Data<br />
■ Technical data (continued)<br />
SIPART PS2<br />
Basic device<br />
without Ex protection<br />
Basic device<br />
with Ex protection<br />
EEx d (flameproof casing)<br />
Basic device<br />
with Ex protection<br />
EEx ia/ib<br />
Basic device<br />
with Ex protection<br />
EEx n<br />
Electrical data<br />
Electrical isolation Between U H and I W Between U H and I W<br />
(2 intrinsically-safe circuits)<br />
Between U H and I W<br />
• Test voltage DC 840 V (1 s) or 700 V (50 Hz, 1 s)<br />
Connections<br />
• Electric Screw terminals 2.5<br />
AWG28-12<br />
Cable bushing M20 or<br />
1/2" NPT (see Ordering<br />
data)<br />
Screw terminals 2.5<br />
AWG28-12<br />
EEx d-certified cable<br />
bushing M20x1.5,<br />
1/2" NPT or M25x1.5<br />
(see Ordering data)<br />
Screw terminals 2.5<br />
AWG28-12<br />
Cable bushing M20 or<br />
1/2" NPT (see Ordering<br />
data)<br />
• Pneumatic<br />
Female thread G1/4 DIN 45 141 or 1/4" 18 NPT (see Ordering data)<br />
• External position sensor<br />
(potentiometer or NSC; option)<br />
-U o – < 5 V<br />
-I o – < 75 mA<br />
-I s – < 160 mA<br />
-P o – < 120 mW<br />
- Max. perm. external capacitance (C o ) – < 1 µF<br />
- Max. perm. external inductance (L o ) – < 1 mH<br />
Screw terminals 2.5<br />
AWG28-12<br />
Cable bushing M20 or<br />
1/2" NPT (see Ordering<br />
data)<br />
116<br />
SIPART PS2 Manual<br />
A5E00074631-03