Technical Data<br />

■ Technical data (continued)<br />

SIPART PS2<br />

Basic device<br />

without Ex protection<br />

Basic device<br />

with Ex protection<br />

EEx d (flameproof casing)<br />

Basic device<br />

with Ex protection<br />

EEx ia/ib<br />

Basic device<br />

with Ex protection<br />

EEx n<br />

Electrical data<br />

Electrical isolation Between U H and I W Between U H and I W<br />

(2 intrinsically-safe circuits)<br />

Between U H and I W<br />

• Test voltage DC 840 V (1 s) or 700 V (50 Hz, 1 s)<br />

Connections<br />

• Electric Screw terminals 2.5<br />

AWG28-12<br />

Cable bushing M20 or<br />

1/2" NPT (see Ordering<br />

data)<br />

Screw terminals 2.5<br />

AWG28-12<br />

EEx d-certified cable<br />

bushing M20x1.5,<br />

1/2" NPT or M25x1.5<br />

(see Ordering data)<br />

Screw terminals 2.5<br />

AWG28-12<br />

Cable bushing M20 or<br />

1/2" NPT (see Ordering<br />

data)<br />

• Pneumatic<br />

Female thread G1/4 DIN 45 141 or 1/4" 18 NPT (see Ordering data)<br />

• External position sensor<br />

(potentiometer or NSC; option)<br />

-U o – < 5 V<br />

-I o – < 75 mA<br />

-I s – < 160 mA<br />

-P o – < 120 mW<br />

- Max. perm. external capacitance (C o ) – < 1 µF<br />

- Max. perm. external inductance (L o ) – < 1 mH<br />

Screw terminals 2.5<br />

AWG28-12<br />

Cable bushing M20 or<br />

1/2" NPT (see Ordering<br />

data)<br />

116<br />

SIPART PS2 Manual<br />

A5E00074631-03