Preparing for Operation<br />
3.6.5 Automatic initialization of rotary actuator<br />
If you can move the actuator correctly through the actuating range,<br />
leave it standing in a central position and start automatic initialization:<br />
1. Press the operation mode key for longer than 5 s. This brings<br />
you to the Configuration operating mode.<br />
Display<br />
2. Set the parameter with the -key to ”turn”<br />
Display:<br />
3. Switch to the second parameter by pressing the operation mode<br />
key briefly. This has set automatically to 90°.<br />
Display:<br />
4. Switch on to the following display with the operation mode key :<br />
5. Start initialization by pressing the key for longer than 5 s.<br />
Display:<br />
During the initialization phase ”RUN1” to”RUN5” appear one after<br />
another in the bottom display (see also structograms in figure 3-33,<br />
page 74 to figure 3-36, page 77).<br />
. NOTE<br />
The initialization process may last up to 15 minutes depending on the<br />
actuator.<br />
SIPART PS2 Manual<br />
A5E00074631-03<br />