Operation<br />

31 VENT1<br />

32 VENT2<br />

Number of cycles pre--<strong>control</strong> valve 1<br />

and<br />

Number of cycles pre--<strong>control</strong> valve 2<br />

These two counters add up the <strong>control</strong> processes of the pre--<strong>control</strong><br />

<strong>valves</strong>.<br />

33 STORE<br />

Store maintenance data<br />

A store function is triggered by pressing the increment key for at<br />

least 5 seconds. Here the diagnostic data 7 to 17 are stored in a non--<br />

volatile memory as ”Data of the last maintenance”. These diagnostic<br />

data are selected values, the changes of which can provide information<br />

on the mechanical wear of the valve.<br />

Normally this function is operated via PDF, menu item Instrument!Store<br />

maintenance info. It is possible to compare the data of the<br />

last maintenance with the current data via PDM.<br />

34 PRUP<br />

35 PRDN<br />

Prediction up<br />

Prediction down<br />

see chapter 4.7 page 110).<br />

36 WT00 to<br />

43 WT95<br />

Setting<br />

range<br />

section<br />

Number of operating hours in distance class WT00 to WT95<br />

If the positioner is in automatic mode, statistics are constantly kept for<br />

how long a valve or a flap has been operated in which section of the<br />

setting range. To do this, the total setting range (0 to 100%) is divided<br />

into 8 sections (distance classes). The positioner continuously registers<br />

the current position and increments the operating hours meter<br />

assigned to the corresponding section (distance class) every hour. This<br />

allows returns to previous operating conditions and is particularly used<br />

to evaluate the <strong>control</strong> properties of the <strong>control</strong> circuit or the entire fitting.<br />

The setting range is divided as follows:<br />

WT00 WT05 WT10 WT30 WT50 WT70 WT90 WT95<br />

≥5 % ≥10 % ≥30 % ≥50 % ≥30 % ≥90 % ≥95 %<br />