Operation<br />
31 VENT1<br />
32 VENT2<br />
Number of cycles pre--<strong>control</strong> valve 1<br />
and<br />
Number of cycles pre--<strong>control</strong> valve 2<br />
These two counters add up the <strong>control</strong> processes of the pre--<strong>control</strong><br />
<strong>valves</strong>.<br />
33 STORE<br />
Store maintenance data<br />
A store function is triggered by pressing the increment key for at<br />
least 5 seconds. Here the diagnostic data 7 to 17 are stored in a non--<br />
volatile memory as ”Data of the last maintenance”. These diagnostic<br />
data are selected values, the changes of which can provide information<br />
on the mechanical wear of the valve.<br />
Normally this function is operated via PDF, menu item Instrument!Store<br />
maintenance info. It is possible to compare the data of the<br />
last maintenance with the current data via PDM.<br />
34 PRUP<br />
35 PRDN<br />
Prediction up<br />
Prediction down<br />
see chapter 4.7 page 110).<br />
36 WT00 to<br />
43 WT95<br />
Setting<br />
range<br />
section<br />
Number of operating hours in distance class WT00 to WT95<br />
If the positioner is in automatic mode, statistics are constantly kept for<br />
how long a valve or a flap has been operated in which section of the<br />
setting range. To do this, the total setting range (0 to 100%) is divided<br />
into 8 sections (distance classes). The positioner continuously registers<br />
the current position and increments the operating hours meter<br />
assigned to the corresponding section (distance class) every hour. This<br />
allows returns to previous operating conditions and is particularly used<br />
to evaluate the <strong>control</strong> properties of the <strong>control</strong> circuit or the entire fitting.<br />
The setting range is divided as follows:<br />
WT00 WT05 WT10 WT30 WT50 WT70 WT90 WT95<br />
≥5 % ≥10 % ≥30 % ≥50 % ≥30 % ≥90 % ≥95 %<br />