Preparing for Operation<br />
2<br />
actuator moves<br />
into closed<br />
position<br />
RUN 2<br />
tolerance band<br />
4% < dw < 10%<br />
?<br />
yes<br />
no<br />
turn slip clutch<br />
until 0 appears<br />
in the bottom line<br />
of the display<br />
continue with:<br />
actuator moves<br />
into open<br />
position<br />
hard stop<br />
up < 97 % ?<br />
no<br />
yes<br />
span<br />
up--dw > 25 % ?<br />
no<br />
continue with:<br />
check<br />
mechanics<br />
1<br />
3<br />
yes<br />
continue with:<br />
<strong>manual</strong> intervention<br />
Figure 3-34<br />
Automatic initialization part 2 (in rotary actuators)<br />