Operation<br />

8 Monitoring of the dead zone adaptation<br />

If the dead zone increases unproportionally in operation in automatic<br />

adaptation of the dead zone (parameter DEBA = Auto) this points to an<br />

error in the system (e.g. a marked increase in stuffing box friction, play<br />

in the displacement detection, leakage). Therefore a limit value can be<br />

specified for this value (”54. DEBA”, limit value for dead zone<br />

monitoring) which activates the fault message output when it is<br />

exceeded.<br />

4.6 Meanings of other display texts<br />

Notes on the tables:<br />

nn<br />

stands for variable numerical values<br />

Fault symbol<br />

/ (slash): the texts to the left and right of the slash<br />

flash alternately<br />

Reports before initializing (first commissioning):<br />

Upper<br />

line<br />

Lower<br />

line<br />

Meaning/Cause<br />

Actions<br />

CPU<br />

START<br />

x<br />

x<br />

Report after connecting the electrical<br />

auxiliary power<br />

P nnn.n x Potentiometer voltage for non-initialized<br />

positioner (P <strong>manual</strong> mode) (Setting<br />

actual value in % of measurement<br />

range)<br />

P------ x Measurement range exceeded, potentiometer<br />

is in the inactive zone,<br />

transmission ratio selector or effective<br />

lever arm are not matched to the<br />

travel<br />

S· Wait<br />

NOINI x Positioner not initialized S Start initialization<br />

S Check using the ”+” and ”--” keys<br />

whether the overall travel can be traversed<br />

without ever ”P------” being displayed<br />

S Perform initialization<br />

S Set transmission ratio selector to 90<br />

degrees, in particular for rotary actuators<br />

S Match effective arm length for linear<br />

actuators to measurement range<br />

Messages during initialization:<br />

Upper<br />

line<br />

Lower<br />

line<br />

Meaning/Cause<br />

Actions<br />

P---- x See above See above<br />

RUN 1 x Initialization started, part 1 active S Wait<br />

(direction of <strong>control</strong> action being determined)<br />

RUN 2 x Initialization part 2 active<br />

(travel check and determination of<br />

the end stops)<br />

S Wait<br />

106<br />

SIPART PS2 Manual<br />

A5E00074631-03