Operation<br />
8 Monitoring of the dead zone adaptation<br />
If the dead zone increases unproportionally in operation in automatic<br />
adaptation of the dead zone (parameter DEBA = Auto) this points to an<br />
error in the system (e.g. a marked increase in stuffing box friction, play<br />
in the displacement detection, leakage). Therefore a limit value can be<br />
specified for this value (”54. DEBA”, limit value for dead zone<br />
monitoring) which activates the fault message output when it is<br />
exceeded.<br />
4.6 Meanings of other display texts<br />
Notes on the tables:<br />
nn<br />
stands for variable numerical values<br />
Fault symbol<br />
/ (slash): the texts to the left and right of the slash<br />
flash alternately<br />
Reports before initializing (first commissioning):<br />
Upper<br />
line<br />
Lower<br />
line<br />
Meaning/Cause<br />
Actions<br />
CPU<br />
START<br />
x<br />
x<br />
Report after connecting the electrical<br />
auxiliary power<br />
P nnn.n x Potentiometer voltage for non-initialized<br />
positioner (P <strong>manual</strong> mode) (Setting<br />
actual value in % of measurement<br />
range)<br />
P------ x Measurement range exceeded, potentiometer<br />
is in the inactive zone,<br />
transmission ratio selector or effective<br />
lever arm are not matched to the<br />
travel<br />
S· Wait<br />
NOINI x Positioner not initialized S Start initialization<br />
S Check using the ”+” and ”--” keys<br />
whether the overall travel can be traversed<br />
without ever ”P------” being displayed<br />
S Perform initialization<br />
S Set transmission ratio selector to 90<br />
degrees, in particular for rotary actuators<br />
S Match effective arm length for linear<br />
actuators to measurement range<br />
Messages during initialization:<br />
Upper<br />
line<br />
Lower<br />
line<br />
Meaning/Cause<br />
Actions<br />
P---- x See above See above<br />
RUN 1 x Initialization started, part 1 active S Wait<br />
(direction of <strong>control</strong> action being determined)<br />
RUN 2 x Initialization part 2 active<br />
(travel check and determination of<br />
the end stops)<br />
S Wait<br />