Design and Functional Principle<br />

. NOTE<br />

15. Drive the actuator to the second desired mechanical position.<br />

16. Adjust the bottom actuating disc (7.3) by hand until the output signal<br />

on terminals 51 and 52 changes.<br />

If you turn the actuating disc beyond the switching point up to the next<br />

switching point, you can set a high-low or a low-high change.<br />

To avoid the actuating discs being accidentally adjusted during operating,<br />

they are relatively sluggish. The following remedy might be of help<br />

if you are having trouble with the adjustment: open and close the actuator<br />

several times while holding the actuating discs. This temporarily<br />

reduces the friction. This allows an easier and finer adjustment.<br />

EMC filter module<br />

for connection of<br />

external position<br />

sensor<br />

The positioner can also be driven by an external position sensor (pot<br />

ent iom et er or NCS ) ( s ee page 40 ) . A n E M C f ilt er m odule, or der num -<br />

ber C73451--A430--D23, is required for this.<br />