Design and Functional Principle<br />
. NOTE<br />
15. Drive the actuator to the second desired mechanical position.<br />
16. Adjust the bottom actuating disc (7.3) by hand until the output signal<br />
on terminals 51 and 52 changes.<br />
If you turn the actuating disc beyond the switching point up to the next<br />
switching point, you can set a high-low or a low-high change.<br />
To avoid the actuating discs being accidentally adjusted during operating,<br />
they are relatively sluggish. The following remedy might be of help<br />
if you are having trouble with the adjustment: open and close the actuator<br />
several times while holding the actuating discs. This temporarily<br />
reduces the friction. This allows an easier and finer adjustment.<br />
EMC filter module<br />
for connection of<br />
external position<br />
sensor<br />
The positioner can also be driven by an external position sensor (pot<br />
ent iom et er or NCS ) ( s ee page 40 ) . A n E M C f ilt er m odule, or der num -<br />
ber C73451--A430--D23, is required for this.<br />
SIPART PS2 Manual<br />
A5E00074631-03<br />
27