Operation<br />

YNRM = MPOS or YNRM = FLOW<br />

Presetting: YA = 0% and YE = 100%<br />

4mA<br />

0%<br />

0mm<br />

YA = 0%<br />

20%<br />

16mm<br />

40%<br />

32mm<br />

50%<br />

7.2mA 10.4mA 13.6mA 16.8mA<br />

60%<br />

48mm<br />

80%<br />

64mm<br />

20mA<br />

100%<br />

80mm<br />

Input current<br />

(setpoint)<br />

X display<br />

W display<br />

Mechan. Stroke<br />

(actual value)<br />

YE = 100%<br />

Example:<br />

YNRM = MPOS with YA = 10 % and YE = 80 %<br />

4mA<br />

0%<br />

0mm<br />

20%<br />

16mm<br />

40%<br />

32mm<br />

50%<br />

7.2mA 10.4mA 13.6mA 16.8mA<br />

YA = 10%<br />

60%<br />

48mm<br />

80%<br />

64mm<br />

YE = 80%<br />

20mA<br />

100%<br />

80mm<br />

Input current<br />

(setpoint)<br />

X display<br />

W display<br />

Mechan. Stroke<br />

(actual value)<br />

Example:<br />

YNRM = FLOW with YA = 10 % and YE = 80 %<br />

4mA<br />

0mm<br />

0%<br />

20%<br />

16mm<br />

YA = 10%<br />

40%<br />

32mm<br />

50%<br />

7.2mA 10.4mA 13.6mA 16.8mA<br />

60%<br />

48mm<br />

80%<br />

100%<br />

64mm<br />

YE = 80%<br />

20mA<br />

80mm<br />

Input current<br />

(setpoint)<br />

X display<br />

W display<br />

Mechan. Stroke<br />

(actual value)<br />

Figure 4-10<br />

Dependence on the stroke of standardization and on YA and YE in the example of an 80 mm<br />

linear actuator<br />

38.YDIR<br />

Manipulated variable direction of action<br />

The direction of action (rising or falling) of the display and the position<br />

feedback (Iy) can be set with this.<br />

39.YCLS<br />

Tight closing with manipulated variable (see figure 4-9, page 91)<br />

With this function the valve can be driven to the seat with the maximum<br />

actuating force of the actuator (continuous contact of the piezo--<br />

<strong>valves</strong>). The tight closing function can be activated on one side or for<br />

both limit positions. YCLS becomes active when the setpoint is below<br />

the value set with parameter “YCDO” or above that set with parameter<br />

“YCUP”.<br />

SIPART PS2 Manual<br />

A5E00074631-03<br />

93