Operation<br />
YNRM = MPOS or YNRM = FLOW<br />
Presetting: YA = 0% and YE = 100%<br />
4mA<br />
0%<br />
0mm<br />
YA = 0%<br />
20%<br />
16mm<br />
40%<br />
32mm<br />
50%<br />
7.2mA 10.4mA 13.6mA 16.8mA<br />
60%<br />
48mm<br />
80%<br />
64mm<br />
20mA<br />
100%<br />
80mm<br />
Input current<br />
(setpoint)<br />
X display<br />
W display<br />
Mechan. Stroke<br />
(actual value)<br />
YE = 100%<br />
Example:<br />
YNRM = MPOS with YA = 10 % and YE = 80 %<br />
4mA<br />
0%<br />
0mm<br />
20%<br />
16mm<br />
40%<br />
32mm<br />
50%<br />
7.2mA 10.4mA 13.6mA 16.8mA<br />
YA = 10%<br />
60%<br />
48mm<br />
80%<br />
64mm<br />
YE = 80%<br />
20mA<br />
100%<br />
80mm<br />
Input current<br />
(setpoint)<br />
X display<br />
W display<br />
Mechan. Stroke<br />
(actual value)<br />
Example:<br />
YNRM = FLOW with YA = 10 % and YE = 80 %<br />
4mA<br />
0mm<br />
0%<br />
20%<br />
16mm<br />
YA = 10%<br />
40%<br />
32mm<br />
50%<br />
7.2mA 10.4mA 13.6mA 16.8mA<br />
60%<br />
48mm<br />
80%<br />
100%<br />
64mm<br />
YE = 80%<br />
20mA<br />
80mm<br />
Input current<br />
(setpoint)<br />
X display<br />
W display<br />
Mechan. Stroke<br />
(actual value)<br />
Figure 4-10<br />
Dependence on the stroke of standardization and on YA and YE in the example of an 80 mm<br />
linear actuator<br />
38.YDIR<br />
Manipulated variable direction of action<br />
The direction of action (rising or falling) of the display and the position<br />
feedback (Iy) can be set with this.<br />
39.YCLS<br />
Tight closing with manipulated variable (see figure 4-9, page 91)<br />
With this function the valve can be driven to the seat with the maximum<br />
actuating force of the actuator (continuous contact of the piezo--<br />
<strong>valves</strong>). The tight closing function can be activated on one side or for<br />
both limit positions. YCLS becomes active when the setpoint is below<br />
the value set with parameter “YCDO” or above that set with parameter<br />
“YCUP”.<br />
SIPART PS2 Manual<br />
A5E00074631-03<br />
93