Operation<br />
Six valve characteristics are stored in the positioner<br />
S linear (12.SFCT = Lin, factory setting)<br />
S equal percentage 1 : 25 (12.SFCT = 1:25)<br />
S equal percentage 1 : 33 (12.SFCT = 1:33)<br />
S equal percentage 1 : 50 (12.SFCT = 1:50)<br />
S inverse equal percentage 25 : 1 (12.SFCT = n1:25)<br />
S inverse equal percentage 33 : 1 (12.SFCT = n1:33)<br />
S inverse equal percentage 50 : 1 (12.SFCT = n1:50)<br />
S freely adjustable (12.SFCT = FrEE)<br />
13.SL0 to 33.SL20<br />
Setpoint turning points<br />
A <strong>flo</strong>w parameter can be assigned to the respective setpoint turning<br />
value at an interval of 5 %. These points lead to a polygon chain with<br />
20 straight lines which therefore represents a projection of the valve<br />
characteristic.<br />
Tight closing<br />
100%<br />
x<br />
Limit for<br />
tight closing<br />
Example:<br />
39 YVLS = UP<br />
41YCUP = 95.0<br />
90<br />
80<br />
12 SFCT=FrEE<br />
70<br />
60<br />
50<br />
Setpoint turning point<br />
Example:<br />
18 SL5 = 45.0<br />
Modulation duty<br />
12 SFCT=Lin<br />
40<br />
30<br />
Limit for<br />
tight closing<br />
Example:<br />
39 YCLS = DW<br />
40 YCDO = 12.5<br />
20<br />
12 SFCT=1--50<br />
10<br />
0<br />
w<br />
Tight closing<br />
SL 0<br />
0<br />
10 20 30 40 50 60 70 80 90 100 %<br />
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />
Figure 4-9<br />
Setpoint characteristic, manipulated variable standardization and tight closing function<br />
SIPART PS2 Manual<br />
A5E00074631-03<br />
91