07.04.2015 Views

view user manual (pdf) - dyna-flo control valves

view user manual (pdf) - dyna-flo control valves

view user manual (pdf) - dyna-flo control valves

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Operation<br />

The setpoint vertex values can only be input at 12.SFCT=FrEE. You<br />

may only enter a strictly monotonous characteristic, and two consecutive<br />

vertex values must differ by at least 0.2 %.<br />

34.DEBA<br />

Dead zone of the <strong>control</strong>ler<br />

At dEbA = AUto the dead zone in automatic operation is adapted continuously<br />

to the requirements of the <strong>control</strong> circuit. The dead zone is<br />

gradually increased on detecting a <strong>control</strong> oscillation. The reverse<br />

adaptation takes place by a time criterion.<br />

In the other discrete settings the fixed value is used for the dead zone.<br />

35.YA<br />

36.YE<br />

Manipulated variable limiting start (see figure 4-9 and 4-10)<br />

and<br />

Manipulated variable limiting end (see figure 4-9 and 4-10)<br />

With the parameters “YA” and “YE” the mechanical actuating distance<br />

(from stop to stop) is limited to the set values. In this way the mechanical<br />

setting range of the actuator can be limited to the active <strong>flo</strong>w and<br />

the integral saturation of the commanding <strong>control</strong>ler avoided.<br />

. NOTE<br />

YE must always be set to greater than YA.<br />

37.YNRM<br />

Manipulated variable standardization (see figure 4-9 and 4-10)<br />

With limiting of the manipulated variable (by “35.YA” and “36.YE”) two<br />

different scalings are produced for the display and the position feedback<br />

via the current output (MPOS or FLOW).<br />

The MPOS scaling shows the mechanical position (0 to 100%) between<br />

the hard stops of the initialization. This is not affected by the parameters<br />

“35.YA” and “36.YE”. The parameters “35.YA” and “36.YE”<br />

are displayed in the MPOS-scale.<br />

The FLOW-scale is the standardization (0 to 100%) to the range between<br />

“35.YA” and “36.YE”. The setpoint w (0 to 100%) is always referred<br />

to this range. This gives (also by using valve characteristics) a<br />

quasi--<strong>flo</strong>w--proportional display and position feedback Iy.<br />

To calculate the <strong>control</strong> difference, the setpoint is also shown in the appropriate<br />

scale on the display.<br />

92<br />

SIPART PS2 Manual<br />

A5E00074631-03

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!