view user manual (pdf) - dyna-flo control valves
view user manual (pdf) - dyna-flo control valves
view user manual (pdf) - dyna-flo control valves
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Operation<br />
The setpoint vertex values can only be input at 12.SFCT=FrEE. You<br />
may only enter a strictly monotonous characteristic, and two consecutive<br />
vertex values must differ by at least 0.2 %.<br />
34.DEBA<br />
Dead zone of the <strong>control</strong>ler<br />
At dEbA = AUto the dead zone in automatic operation is adapted continuously<br />
to the requirements of the <strong>control</strong> circuit. The dead zone is<br />
gradually increased on detecting a <strong>control</strong> oscillation. The reverse<br />
adaptation takes place by a time criterion.<br />
In the other discrete settings the fixed value is used for the dead zone.<br />
35.YA<br />
36.YE<br />
Manipulated variable limiting start (see figure 4-9 and 4-10)<br />
and<br />
Manipulated variable limiting end (see figure 4-9 and 4-10)<br />
With the parameters “YA” and “YE” the mechanical actuating distance<br />
(from stop to stop) is limited to the set values. In this way the mechanical<br />
setting range of the actuator can be limited to the active <strong>flo</strong>w and<br />
the integral saturation of the commanding <strong>control</strong>ler avoided.<br />
. NOTE<br />
YE must always be set to greater than YA.<br />
37.YNRM<br />
Manipulated variable standardization (see figure 4-9 and 4-10)<br />
With limiting of the manipulated variable (by “35.YA” and “36.YE”) two<br />
different scalings are produced for the display and the position feedback<br />
via the current output (MPOS or FLOW).<br />
The MPOS scaling shows the mechanical position (0 to 100%) between<br />
the hard stops of the initialization. This is not affected by the parameters<br />
“35.YA” and “36.YE”. The parameters “35.YA” and “36.YE”<br />
are displayed in the MPOS-scale.<br />
The FLOW-scale is the standardization (0 to 100%) to the range between<br />
“35.YA” and “36.YE”. The setpoint w (0 to 100%) is always referred<br />
to this range. This gives (also by using valve characteristics) a<br />
quasi--<strong>flo</strong>w--proportional display and position feedback Iy.<br />
To calculate the <strong>control</strong> difference, the setpoint is also shown in the appropriate<br />
scale on the display.<br />
92<br />
SIPART PS2 Manual<br />
A5E00074631-03