Preparing for Operation<br />
Figure 3-5<br />
Favorable and unfavorable installation positions<br />
If conditions oblige you to operate the positioner in a unfavorable<br />
installation position, you can take additional precautionary measures to<br />
prevent penetration by water.<br />
. NOTE<br />
Never clean the positioner with a high pressure water jet because the<br />
IP65 degree of protection is inadequate protection for this.<br />
The necessary additional measures to prevent penetration by water<br />
depend on the installation position chosen and you may additionally<br />
require:<br />
S screw--type gland with sealing ring (e.g. FESTO: CK –1 / 4–PK–6)<br />
S plastic hose approx. 20 to 30 cm (e.g. FESTO PUN-- 8X1,25 SW)<br />
S cable straps (number and length depends on local conditions)<br />
Procedure<br />
S<br />
S<br />
S<br />
S<br />
Connect the pipes in such a way that rain water which runs along<br />
the pipes can drip off before it reaches the terminal strip of the positioner.<br />
Check the electrical connections for perfect firm contact.<br />
Check the seal in the housing cover for damage and contamination.<br />
Clean and replace if necessary.<br />
Mount the positioner if possible so that the sinter bronze silencer<br />
faces downwards on the underside of the housing (vertical installation<br />
position). If this is not possible, the silencer should be replaced<br />
by a suitable screw--type gland with a plastic hose.<br />
SIPART PS2 Manual<br />
A5E00074631-03<br />
39