view user manual (pdf) - dyna-flo control valves
view user manual (pdf) - dyna-flo control valves
view user manual (pdf) - dyna-flo control valves
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Care and Maintenance<br />
Service and Maintenance<br />
5<br />
The positioner is largely maintenance--free. The positioners are fitted<br />
with filters in the pneumatic connections as protection against coarse<br />
particles of dirt. If the pneumatic energy supply contains particles of<br />
dirt, the filters may clog and impair the function of the positioner. In this<br />
case the filters can be cleaned as follows.<br />
Positioner in metal housing and explosion proof version<br />
1. Switch off the pneumatic power supply and remove the pipes.<br />
2. Remove the metal filters carefully from the holes and clean (e.g.<br />
with compressed air).<br />
3. Insert the filters.<br />
4. Re-connect the pipes and supply pneumatic energy.<br />
Positioner in plastic housing<br />
Removal<br />
1. Switch off the pneumatic power supply and remove the pipes.<br />
2. Unscrew the cover<br />
3. Remove the three screws from the pneumatic connector strip.<br />
4. Remove the filters and O-rings behind the connector strip.<br />
5. Clean the filters (e.g. with compressed air).<br />
Installation<br />
6. First insert the filters in the recesses in the plastic housing and then<br />
place the O-rings on the filters.<br />
7. Align the pneumatic connector strip on the two lugs and screw tight<br />
with the three self--tapping screws.<br />
Important:<br />
Make sure that the same thread is used. To do this turn the screws<br />
counterclockwise until they snap into the thread audibly. Only then<br />
should you tighten the screws.<br />
SIPART PS2 Manual<br />
A5E00074631-03<br />
111