Preparing for Operation<br />
The initialization is complete when the following display<br />
appears:<br />
The top value indicates the total angle of rotation of the actuator<br />
(example 93.5°).<br />
The following display appears after pressing the operation mode key<br />
briefly:<br />
To exit the Configuration mode, press the operation mode key for<br />
longer than 5 s. The software version is displayed after about 5 s. The<br />
instrument is in <strong>manual</strong> operation after releasing the operation mode<br />
key.<br />
. NOTE<br />
You can abort an ongoing initialization at any time by pressing the operation<br />
mode key. Your previous settings are retained. All the parameters<br />
are set to the factory setting only after performing a “Preset”.<br />
3.6.6 Manual initialization of rotary actuators<br />
The positioner can be initialized with this function without the actuator<br />
being driven hard against the limit stop. The start and end positions of<br />
the travel are set <strong>manual</strong>ly. The other initialization steps (optimization<br />
of the <strong>control</strong> parameters) run automatically as in automatic initialization.<br />
Manual initialization<br />
procedure in<br />
rotary actuators<br />
1. Make preparations as described in chapter 3.6.4, page 70 for<br />
rotary actuators. In particular, make sure by <strong>manual</strong>ly driving the<br />
whole travel that the displayed potentiometer setting<br />
moves in the permissible range between P5.0 and P95.0.<br />
2. Press the operation mode key for longer than 5 s. This brings<br />
you to the Configuration mode.<br />
Display:<br />
72<br />
SIPART PS2 Manual<br />
A5E00074631-03