Operation<br />
P-<strong>manual</strong> mode<br />
(ex--factory state)<br />
The display of the positioner shows you the current potentiometer<br />
setting in the top line and ”NOINIT” flashes in the second line. You can<br />
move the actuator with the decrement and increment key . In order<br />
to adapt the positioner to your actuator, you have to change to the<br />
Configuration menu. See also chapter 3.6, page 63 “Commissioning”.<br />
Output of alarms and position feedback is possible after successful initialization.<br />
Configuration and<br />
initialization<br />
To go to the Configuration menu, press the operation mode key for<br />
at least 5 seconds. In the Configuration menu you can adapt the<br />
positioner individually to your actuator and start initialization. Only a few<br />
parameters need to be set in the positioner prior to initialization. The<br />
others are defaulted so that they do not normally need to be adjusted.<br />
You can block the Configuration menu against manipulation by an<br />
appropriately parameterized and activated digital input. Which<br />
parameters you need to set and all other parameters are explained in<br />
chapter 4.4, page 84 Parameters.<br />
The configuration mode can be reported by outputting a<br />
parameterizable fault message, a position feedback or output of limit<br />
values A1 and A2 is not possible.<br />
. NOTE<br />
If the electric power supply fails during configuration, the positioner<br />
switches back to the first parameter after recovering the power supply,<br />
values which have already been parameterized are retained. Without a<br />
power failure you re--enter the configuration menu at the point you<br />
exited it when you call the Configuration menu again.<br />
at the same time<br />
at the same time<br />
to<br />
at the same time<br />
at the same time<br />
Figure 4-5<br />
Over<strong>view</strong>: Configuration<br />
SIPART PS2 Manual<br />
A5E00074631-03<br />