Operation<br />

P-<strong>manual</strong> mode<br />

(ex--factory state)<br />

The display of the positioner shows you the current potentiometer<br />

setting in the top line and ”NOINIT” flashes in the second line. You can<br />

move the actuator with the decrement and increment key . In order<br />

to adapt the positioner to your actuator, you have to change to the<br />

Configuration menu. See also chapter 3.6, page 63 “Commissioning”.<br />

Output of alarms and position feedback is possible after successful initialization.<br />

Configuration and<br />

initialization<br />

To go to the Configuration menu, press the operation mode key for<br />

at least 5 seconds. In the Configuration menu you can adapt the<br />

positioner individually to your actuator and start initialization. Only a few<br />

parameters need to be set in the positioner prior to initialization. The<br />

others are defaulted so that they do not normally need to be adjusted.<br />

You can block the Configuration menu against manipulation by an<br />

appropriately parameterized and activated digital input. Which<br />

parameters you need to set and all other parameters are explained in<br />

chapter 4.4, page 84 Parameters.<br />

The configuration mode can be reported by outputting a<br />

parameterizable fault message, a position feedback or output of limit<br />

values A1 and A2 is not possible.<br />

. NOTE<br />

If the electric power supply fails during configuration, the positioner<br />

switches back to the first parameter after recovering the power supply,<br />

values which have already been parameterized are retained. Without a<br />

power failure you re--enter the configuration menu at the point you<br />

exited it when you call the Configuration menu again.<br />

at the same time<br />

at the same time<br />

to<br />

at the same time<br />

at the same time<br />

Figure 4-5<br />

Over<strong>view</strong>: Configuration<br />

SIPART PS2 Manual<br />

A5E00074631-03<br />

83