11-8-3. Indoor Unit (Other Parts)<br />

No.<br />

1<br />

Part name<br />

Room temp. (TA) sensor<br />

Heat exchanger (TC) sensor<br />

Checking procedure<br />

Disconnect the connector and measure the resistance value with tester.<br />

(Normal temp.)<br />

Sensor<br />

TA, TC (kΩ)<br />

Temperature<br />

10°C 20°C 25°C 30°C 40°C<br />

20.7 12.6 10.0 7.9 4.5<br />

2<br />

3<br />

Remote controller<br />

Louver motor<br />

MP24Z<br />

Refer to 11-4-1. (5).<br />

Measure the resistance value of each winding coil by using the tester.<br />

(Under normal temp. 25°C)<br />

Position Resistance value<br />

White 1<br />

Yellow 2<br />

Yellow 3<br />

Yellow 4<br />

Yellow 5<br />

1<br />

2<br />

3<br />

4<br />

5<br />

1 to 2<br />

1 to 3<br />

1 to 4<br />

1 to 5<br />

380 ± 40Ω<br />

4 Indoor fan motor<br />

Refer to 11-4-1. (3) and (4).<br />

11-8-4. Outdoor Unit<br />

No.<br />

1<br />

2<br />

Part name<br />

Compressor<br />

(Model : DA220A2F-20L1)<br />

Outdoor fan motor<br />

(Model : ICF-140-63-2R)<br />

Checking procedure<br />

Measure the resistance value of each winding by using the tester.<br />

Red<br />

Position<br />

Red - White<br />

Resistance value<br />

White - Black 0.2 ± 0.01Ω<br />

Black - Red<br />

White<br />

Black<br />

Under 20°C<br />

Measure the resistance value of winding by using the tester.<br />

Red<br />

1 Yellow<br />

4 Pink<br />

5 Gray<br />

Position<br />

Yellow - Pink<br />

Resistance value<br />

5 to 20 kΩ<br />

White<br />

Black<br />

For details, refer to Section 11-5.<br />

3<br />

4<br />

Compressor thermo.<br />

Bimetal type<br />

(Model : US622KXTMQO)<br />

Outdoor temperature sensor<br />

(TO), pipe temperature<br />

sensor (TGa, TGb, TGc,<br />

TGd), discharge temperature<br />

sensor (TD), suction<br />

temperature sensor (TS),<br />

evaporator temperature<br />

sensor (TE),<br />

Check conduction by using the tester.<br />

Disconnect the connector, and measure resistance value with the tester.<br />

(Normal temperature)<br />

Sensor<br />

TA, TC (kΩ)<br />

Temperature<br />

TO, TE, TS (kΩ)<br />

TGa, TGb, TGc, TGd (kΩ)<br />

10°C 20°C 25°C 40°C 50°C<br />

105 64 51 27 18<br />

20.6 12.6 10.0 5.1 3.4<br />

20.0 12.5 10.0 5.3 3.6<br />

– 104 –