12-3. Outdoor Unit<br />
No.<br />
Part name<br />
Procedure<br />
Remarks<br />
1<br />
Common<br />
procedure<br />
1. Detachment<br />
1) Stop operation of the air conditioner, and turn<br />
“OFF” the power breaker.<br />
2) Remove the side panel. (Ø4 × 10L 3 pcs.)<br />
3) Remove the cord clamp.<br />
(Ø4 × 14L 5 × 2 = 10 pcs.)<br />
Disconnect the connecting cables and power<br />
cord from the terminals.<br />
4) Remove the upper panel. (Ø4 × 10L 6 pcs.)<br />
5) Remove the front panel. (Ø4 × 10L 3 pcs.)<br />
6) Remove the back panel. (Ø4 × 10L 6 pcs.)<br />
7) Remove the air outlet panel. (Ø4 × 10L 8 pcs.)<br />
Air outlet panel<br />
Fan<br />
guard<br />
4<br />
Front panel<br />
Upper panel<br />
Back panel<br />
Side panel<br />
2 Inverter<br />
assembly<br />
1. Detachment<br />
1) Perform work from item 1) to 5) of 1 .<br />
2) Remove screw (ST1T Ø4 × 10L 1 pc.) of the<br />
upper left part of the inverter cover.<br />
• If removing the inverter cover in this condition,<br />
P.C. board can be checked.<br />
• If there is no space in the upper part of the<br />
upper cabinet, perform work from 6) to 7) of<br />
1 and remove the partition fixing plate<br />
(ST1T Ø4 × 10L 1 pc.).<br />
Be careful to check the inverter because<br />
high-voltage circuit is incorporated in it.<br />
3) Perform discharging by connecting the discharging<br />
resistance (approx. 100Ω 40W) or<br />
plug of soldering iron to , terminals of the<br />
C15 (printed “CAUTION HIGH VOLTAGE” is<br />
attached.) electrolytic capacitor (760µF) on<br />
P.C. board.<br />
Be careful to discharge the capacitor because<br />
the electrolytic capacitor cannot<br />
naturally discharge and voltage remains<br />
according to trouble type in some cases.<br />
Inverter cover<br />
P.C. board<br />
(Soldered surface)<br />
Fixing plate<br />
(Partition)<br />
NOTE<br />
This capacitor is one with mass capacity.<br />
Therefore, it is dangerous that a large spark<br />
generates if short-circuiting between ,<br />
polarity with screwdriver, etc. for discharging.<br />
The holder at upper part.<br />
4) Remove screw (Ø4 × 10L 2 pcs.) fixing the<br />
valve clamping plate/the inverter box, and<br />
fixing the back panel/the inverter box.<br />
5) Remove various lead wires from the holder at<br />
upper part of the inverter box and cut 2 tie-lap<br />
ties binding each lead wires :<br />
6) Pull the inverter box upward.<br />
7) Disconnect connectors of various lead wires.<br />
Tie-lap ties (2 pcs)<br />
– 116 –