2-2-1. Operation Characteristic Curve<br />
<br />
<br />
Current (A)<br />
16<br />
14<br />
12<br />
10<br />
8<br />
6<br />
4<br />
• Conditions<br />
Indoor : DB27˚C/WB19˚C<br />
Outdoor : DB35˚C<br />
Air flow : High<br />
Pipe length: 5m x 4<br />
4 units operating<br />
220V<br />
230V<br />
240V<br />
Current (A)<br />
14<br />
12<br />
10<br />
8<br />
6<br />
4<br />
• Conditions<br />
Indoor : DB20˚C<br />
Outdoor : DB7˚C / WB6˚C<br />
Air flow : High<br />
Pipe length: 5m x 4<br />
4 units operating<br />
230V<br />
220V<br />
240V<br />
2<br />
2<br />
0<br />
0 10 20 30 40 50 60 70 80<br />
Inverter output frequency (rps)<br />
0<br />
0 10 20 30 40 50 60 70 80 90 100<br />
Inverter output frequency (rps)<br />
2-2-2. Capacity Variation Ratio According to Outdoor Temperature<br />
<br />
<br />
Cooling capacity ratio (%)<br />
110<br />
100<br />
90<br />
80<br />
70 • Conditions<br />
Indoor : DB27˚C/WB19˚C<br />
Indoor air flow : High<br />
60<br />
Pipe length : 5m x 4<br />
4 units operating<br />
50<br />
32 33 34 35 36 37 38 39 40 41 42 43 44<br />
Outdoor temp. (˚C)<br />
Current limited start<br />
Heating capacity ratio (%)<br />
110<br />
100<br />
90<br />
80<br />
70<br />
60<br />
• Conditions<br />
Indoor : DB20˚C<br />
Air flow : High<br />
Pipe length : 5m x 4<br />
4 units operating<br />
50<br />
-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10<br />
Outdoor temp. (˚C)<br />
2-2-3. Capacity Variation Ratio According to Pipe Length<br />
<br />
<br />
110<br />
110<br />
Coolimg capacity ratio (%)<br />
105<br />
100<br />
95<br />
90<br />
85<br />
Standard pipe length 20m<br />
• Conditions<br />
Indoor : DB27˚C/WB19˚C<br />
Outdoor : DB35˚C<br />
Indoor air flow : High<br />
4 units operating<br />
Heating capacity ratio (%)<br />
105<br />
100<br />
95<br />
90<br />
85<br />
Standard pipe length 20m<br />
• Conditions<br />
Indoor : DB20˚C<br />
Outdoor : DB7˚C/WB6˚C<br />
Indoor air flow : High<br />
4 units operating<br />
80 0 10 20 30 40 50 60 70 80<br />
Total pipe length (m)<br />
80 0 10 20 30 40 50 60 70 80<br />
Total pipe length (m)<br />
– 23 –