RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E / RAS-4M27GACV-E<br />
Unit model<br />
Indoor<br />
RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E<br />
Outdoor<br />
RAS-4M27GACV-E<br />
Cooling capacity (kW) 8.0<br />
Cooling capacity range (kW) 1.4 – 9.2<br />
Heating capacity (kW) —<br />
Heating capacity range (kW) —<br />
Power supply<br />
220–240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz<br />
Unit model RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E<br />
Indoor<br />
Running current (A) 0.15 0.15 0.15<br />
Power consumption (W) 30 30 30<br />
Power factor (%) 91/87/83 91/87/83 91/87/83<br />
Electric<br />
Unit model<br />
RAS-4M27GACV-E<br />
characteristics<br />
Running current (A) 11.60/11.09/10.63<br />
Outdoor Power consumption (W) 2500<br />
Power factor (%) 98<br />
Starting current (A) 11.60/11.09/10.63<br />
COP 3.20<br />
Unit model RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E<br />
High (dB•A) 42 43 45<br />
Indoor<br />
Operating<br />
Medium (dB•A) 33 34 36<br />
noise<br />
Low (dB•A) 27 27 29<br />
Outdoor<br />
Unit model<br />
RAS-4M27GACV-E<br />
Full indoor units operating (dB•A) 48<br />
Unit model RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E<br />
Height (mm) 250 250 250<br />
Dimension Width (mm) 790 790 790<br />
Indoor unit<br />
Depth (mm) 215 215 215<br />
Net weight (kg) 9 9 9<br />
Fan motor output (W) 30 30 30<br />
Air flow rate (m³/h) 550 560 640<br />
Unit model<br />
RAS-4M27GACV-E<br />
Height (mm) 795<br />
Dimension Width (mm) 900<br />
Depth (mm) 320<br />
Net weight (kg) 63<br />
Outdoor unit<br />
Motor output (W) 2000<br />
Compressor Type<br />
Twin rotary type with DC-inverter variable speed control<br />
Model<br />
DA220A2F-20L<br />
Fan motor output (W) 60<br />
Air flow rate (m³/h) High : 3000, Medium : 2800<br />
Type<br />
Flare connection<br />
Indoor unit<br />
Unit model RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E<br />
Liquid side/Gas side Ø6.35/ Ø9.52 Ø6.35/ Ø9.52 Ø6.35/ Ø12.7<br />
Unit model<br />
RAS-4M27GACV-E<br />
A unit liquid side/Gas side Ø6.35/ Ø12.7<br />
Outdoor unit B unit liquid side/Gas side Ø6.35/ Ø9.52<br />
C unit liquid side/Gas side Ø6.35/ Ø9.52<br />
Piping<br />
D unit liquid side/Gas side Ø6.35/ Ø9.52<br />
connection<br />
Maximum length (per unit) (m) 25<br />
Maximum length (total) (m) 70<br />
Maximum chargeless length (m) 70<br />
Maximum height difference (m) 15<br />
Name of refrigerant<br />
R410A<br />
Weight (kg) 2.2<br />
Wiring connection<br />
Power supply<br />
3 Wires : includes earth<br />
Interconnection<br />
4 Wires : includes earth<br />
Usable temperature range<br />
Indoor (°C) 21 to 32<br />
Outdoor (°C) 10 to 43<br />
Unit model RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E<br />
Installation plate 1 1 1<br />
Wireless remote controller 1 1 1<br />
Batteries 2 2 2<br />
Remote controller holder 1 1 1<br />
Indoor unit Zeolite-plus filter 1 1 1<br />
Accessory<br />
Plasma pure filter 1 1 1<br />
Remote controller holder mounting screw 2 (Ø3.1 × 16L) 2 (Ø3.1 × 16L) 2 (Ø3.1 × 16L)<br />
Owner’s manual 1 1 1<br />
Mounting screw 6 (Ø4 × 25L) 6 (Ø4 × 25L) 6 (Ø4 × 25L)<br />
Installation manual 1 1 1<br />
Unit model<br />
RAS-4M27GACV-E<br />
Outdoor unit Installation manual<br />
Specifications<br />
1<br />
1<br />
• For performance when each indoor unit is combined with other unit, refer to the separate table.<br />
• The specifications may be subject to change without notice for purpose of improvement.<br />
– 7 –