Outdoor Unit : RAS-4M27GAV-E<br />

<br />

Temperature<br />

condition<br />

Indoor<br />

Outdoor<br />

No. of<br />

operating<br />

units<br />

Operating combination<br />

(Unit)<br />

A B C D<br />

Standard<br />

pressure<br />

P (MPa)<br />

Heat exchanger<br />

pipe temp.<br />

T1 (°C)<br />

T2 (°C)<br />

Indoor<br />

fan<br />

Outdoor<br />

fan<br />

Compressor<br />

revolution<br />

(rps)<br />

1 unit<br />

10 – – – 2.7 to 2.9 44 to 46 2 to 4 High MED 41<br />

13 – – – 3.2 to 3.4 52 to 54 2 to 4 High MED 52<br />

16 – – – 3.6 to 3.9 53 to 55 2 to 4 High MED 56<br />

2 units<br />

10 10 – – 2.7 to 2.9 45 to 47 0 to 2 High MED 62<br />

13 10 – – 2.8 to 3.0 45 to 47 0 to 2 High MED 64<br />

16 10 – – 2.9 to 3.1 46 to 48 0 to 2 High MED 66<br />

13 13 – – 2.9 to 3.1 46 to 48 0 to 2 High MED 67<br />

16 13 – – 3.0 to 3.2 47 to 49 –1 to 1 High MED 69<br />

16 16 – – 3.1 to 3.3 48 to 50 –1 to 1 High MED 71<br />

3 units<br />

10 10 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 72<br />

13 10 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 72<br />

16 10 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 72<br />

13 13 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73<br />

20 / – 7 / 6<br />

16 13 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73<br />

13 13 13 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73<br />

16 16 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73<br />

16 13 13 – 2.5 to 2.7 37 to 39 –2 to 0 High MED 74<br />

16 16 13 – 2.5 to 2.7 37 to 39 –2 to 0 High MED 74<br />

16 16 16 – 2.5 to 2.7 37 to 39 –2 to 0 High MED 74<br />

4 units<br />

10 10 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 72<br />

13 10 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 72<br />

16 10 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73<br />

13 13 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73<br />

16 13 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73<br />

13 13 13 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73<br />

16 13 13 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 74<br />

16 16 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 74<br />

NOTES :<br />

1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.<br />

(Thermistor themometer)<br />

2. Connecting piping condition : 5 meters × 4 units (5m/each indoor unit)<br />

– 41 –