General 07/03 Kollmorgen<br />
1.7.1 External fusing<br />
Fusible cutouts or similar<br />
AC feed FN1/2/3 16 A slow<br />
24V feed FH1/2 16 A slow<br />
regen resistor FB1/2 6 A slow<br />
1.7.2 Permissible ambient conditions, ventilation, mounting position<br />
Storage temp. / humidity / duration � p.65<br />
Transport temperature / humidity � p.65<br />
Supply voltage tolerances<br />
main power<br />
<strong>SERVOSTAR</strong> 40xM<br />
<strong>SERVOSTAR</strong> 44xM<br />
auxiliary supply<br />
w/o brake, w/o fan<br />
with brake or fan<br />
Ambient temperature in operation<br />
min 1x115V-10% AC / max 1x230V +10% , 50/60 Hz<br />
min 3x115V-10% AC / max 3x230V +10% , 50/60 Hz<br />
min 3x230V-10% AC / max 3x<strong>400</strong>V +10% , 50/60 Hz<br />
20 VDC ... 30 VDC<br />
24 VDC (-0% +15%)<br />
0...+45 o C at rated conditions<br />
+45...+55°C with power derating 2.5% / K<br />
Humidity in operation rel. humidity 85%, no condensation<br />
up to 1000m amsl without restrictions<br />
Site altitude<br />
1000...2500m amsl with derating<br />
1.5% / 100m<br />
Pollution level Pollution level 2 as per EN 60204 / EN 50178<br />
Enclosure rating IP 20<br />
Mounting position normally vertical � p.24<br />
Ventilation<br />
free convection for <strong>SERVOSTAR</strong>4x3,<br />
add-on fan (� p.66) required for <strong>SERVOSTAR</strong>4x6<br />
Make sure that there is adequate forced ventilation within the closed switchgear cabinet.<br />
1.7.3 Conductor cross-sections<br />
Following EN 60204-1, we recommend for single-axis systems:<br />
AC connection 4 mm², depending on the system fusing<br />
Motor cables 1 mm², shielded, capacitance