Kollmorgen 07/03 Appendix<br />
Fault possible causes<br />
measures to remove the cause of<br />
the fault<br />
— wrong cable<br />
— check wiring<br />
F25 message: — wrong phasing<br />
— check resolver poles (RESPOLES)<br />
Commutation error<br />
check motor poles (MPOLES)<br />
check offset (MPHASE)<br />
F27 message: — -AS-24V relay AND hardware enable AND — check PLC programming and<br />
error AS-option<br />
software enable are active<br />
wiring<br />
— servo amplifier not enabled<br />
— apply enable signal<br />
— break in setpoint cable<br />
— check setpoint cable<br />
— motor phases swapped<br />
— correct motor phase sequence<br />
motor does not rotate — brake not released<br />
— check brake control<br />
— drive is mechanically blocked<br />
— check mechanism<br />
— no. of motor poles set incorrectly<br />
— set no. of motor poles<br />
— feedback set up incorrectly<br />
— set up feedback correctly<br />
— gain too high (speed controller)<br />
— reduce Kp (speed controller)<br />
motor oscillates — shielding in feedback cable has a break — replace feedback cable<br />
— AGND not wired up<br />
— join AGND to CNC-GND<br />
drive reports<br />
following error<br />
—<br />
—<br />
Irms or Ipeak is set to low<br />
setpoint ramp is too long<br />
—<br />
—<br />
increase Irms or Ipeak<br />
(keep within motor data !)<br />
shorten setpoint ramp +/motor<br />
overheating — Irms/Ipeak set too high — reduce Irms/Ipeak<br />
— Kp (speed controller) too low<br />
— increase Kp (speed controller)<br />
— Tn (speed controller) too high<br />
— use motor default value for<br />
drive too soft<br />
Tn (speed controller)<br />
— PID-T2 too high<br />
— reduce PID-T2<br />
— T-Tacho too high<br />
— reduce T-Tacho<br />
— Kp (speed controller) too high<br />
— reduce Kp (speed controller)<br />
drive runs<br />
roughly<br />
—<br />
—<br />
Tn (speed controller) too low<br />
PID-T2 too low<br />
—<br />
—<br />
use motor default value for<br />
Tn (speed controller)<br />
increase PID-T2<br />
— T-Tacho too low<br />
— increase T-Tacho<br />
— offset not correctly adjusted for analog — adjust setpoint-offset (analog I/O)<br />
axis drifts at<br />
setpoint provision<br />
setpoint = 0V — AGND not joined to the CNC-GND of the<br />
controls<br />
— join AGND and CNC-GND<br />
n12 message:<br />
Motor default values<br />
loaded<br />
— Motor number stored in sine encoders<br />
EEPROM different than what drive is<br />
configured for<br />
— If n12 is displayed, default values<br />
for the motor are loaded.<br />
Motor number will be automatically<br />
stored in EEPROM with SAVE.<br />
n14 message:<br />
Wake & shake active<br />
— Wake & shake not executed — Enable the drive<br />
<strong>SERVOSTAR</strong> ® <strong>400</strong> Installation manual 69