Commissioning 07/03 Kollmorgen<br />
The following instructions should help you to carry out the commissioning in a sensible order, without<br />
any hazards to people or machinery.<br />
Check installation<br />
Negate enable signal<br />
Switch on 24V<br />
aux. supply<br />
Switch on PC, start<br />
setup S/W<br />
Check the displayed<br />
parameters, and<br />
correct them if<br />
necessary<br />
See Chapter 2. Disconnect the servo amplifier from the supply.<br />
0V on terminal X1/3 (Enable)<br />
24V DC on terminal 0/1, ground on terminal X0/2<br />
After the initialization procedure (about 0.5 sec.) the status is<br />
shown in the LED display (� p.58)<br />
Select the interface to which the servo amplifier is connected.<br />
The parameters which are stored in the SRAM of the servo<br />
amplifier are transferred to the PC.<br />
Caution !<br />
Check the parameters described below especially carefully.<br />
If you ignore these basic data, system components may be<br />
damaged or destroyed.<br />
Supply voltage : set to the actual mains supply voltage<br />
(observe supply voltage limits, � p.17)<br />
Rated motor voltage : at least as high as the DC-link voltage of the amplifier<br />
Motor pole-no. : must match the motor (see motor manual)<br />
Feedback : must match the feedback unit in the motor<br />
IRMS<br />
: maximum is the motor standstill current I0 (as on nameplate)<br />
IPEAK<br />
: maximum is 4 x motor standstill current I0<br />
Limit speed : maximum is the rated motor speed (as on nameplate)<br />
Regen power : maximum is the rated dissipation for the regen resistor<br />
Station address : unique address on the master<br />
Check safety devices<br />
Switch on power<br />
Apply 0V setpoint<br />
Enable amplifier<br />
Setpoint<br />
Optimization<br />
Commission fieldbus<br />
Caution !<br />
Make sure that any unintended movement of the drive<br />
cannot cause danger to machinery or personnel.<br />
through the ON/OFF button of the contactor control<br />
apply 0V to terminals X3/2-3<br />
(500 msec after switching on the supply power) 24V DC on<br />
terminal X1/3 (Enable), motor is at rest with standstill torque M0<br />
apply a small analog setpoint (about 0.5V is recommended) to<br />
terminals X3/2-3<br />
If the motor oscillates, the Kp parameter in the screen page<br />
Speed controller must be reduced – the motor is in danger !<br />
optimize the speed, current and position controllers<br />
see commissioning instructions in the corresponding<br />
manual on the CD-ROM<br />