Kollmorgen 07/03 Commissioning<br />

4.2 Parameterization<br />

A default parameter set is loaded into your servo amplifier at the factory. This contains valid and<br />

safe parameters for the current and speed controllers.<br />

A database for motor parameters is stored in the servo amplifier. During commissioning you must<br />

select the data set for the motor that is connected and store it in the servo amplifier. For most applications<br />

these settings will already provide good to very good control loop characteristics.<br />

An exact description of all parameters and the options for optimizing the control loop characteristics<br />

can be found in the manual “Setup Software DRIVE.EXE”.<br />

4.2.1 Multi-axis systems<br />

Axis module 1<br />

X8<br />

PC<br />

All the axes in a system can be parameterized through the RS232 interface in the master. To do<br />

this, there is an internal connection between the master and the axis modules. The PC cable only<br />

has to be connected to the master.<br />

The internal address assignment is carried out automatically, so that it is only necessary to set up<br />

the basic station address for the master.<br />

Axis module 2<br />

Axis module 3<br />

Master<br />

COMx<br />

RS232<br />

After changing the station address it is necessary to turn off the 24V auxiliary<br />

supply, and then turn it on again.<br />

Starting at the master, descending addresses are assigned automatically to the axis modules. The<br />

following table shows an example with one master and three axis modules:<br />

Axis Address Remark<br />

Master 10 Master address, set by user<br />

Axis module 3 9<br />

Axis module 2 8 assigned automatically<br />

Axis module 1 7<br />

The highest permitted master address is 128. When choosing the master address, please<br />

consider that at least address 1 will be assigned to the last (leftmost) axis module.<br />

In CAN and PROFIBUS field bus systems the automatically assigned addresses must<br />

not match the address of other nodes.<br />

<strong>SERVOSTAR</strong> ® <strong>400</strong> Installation manual 57<br />