<strong>Code</strong> 21 PROCEDURES FOR INSPECTION,<br />
TESTING AND CERTIFICATION<br />
21A Inspection <strong>of</strong> Low Voltage Installations<br />
A visual inspection should be made to verify that <strong>the</strong> electrical equipment as<br />
installed is correctly selected and erected in accordance with <strong>the</strong> <strong>Wiring</strong><br />
<strong>Regulations</strong> and this CoP, and that <strong>the</strong>re is no apparent damage. The visual<br />
inspection should include a check on <strong>the</strong> following items, where appropriate:<br />
(a) adequacy <strong>of</strong> working space, access, and maintenance facilities,<br />
(b) connections <strong>of</strong> conductors,<br />
(c) identification <strong>of</strong> conductors,<br />
(d ) adequacy <strong>of</strong> <strong>the</strong> sizes <strong>of</strong> conductor in relation to current carrying capacity<br />
and voltage drop,<br />
(e) correct connections <strong>of</strong> all equipment with special attention to socket<br />
outlets, lampholders, isolators, switches, residual current devices,<br />
miniature circuit breakers, and protective conductors,<br />
(f ) presence <strong>of</strong> fire barriers and protection against <strong>the</strong>rmal effects,<br />
(g) methods <strong>of</strong> protection against direct contact with live parts (including<br />
measurement <strong>of</strong> distances where appropriate), i.e. protection by<br />
insulation <strong>of</strong> live parts, or protection by barriers or enclosures,<br />
(h) presence <strong>of</strong> appropriate devices <strong>for</strong> isolation and switching,<br />
(i) choice and setting <strong>of</strong> protective and indicative devices,<br />
( j) labelling <strong>of</strong> circuits, fuses, protective devices, switches, isolators and<br />
terminals,<br />
(k) selection <strong>of</strong> equipment and protective measures appropriate to adverse<br />
environmental conditions,<br />
(l) presence <strong>of</strong> danger and warning notices,<br />
(m) presence <strong>of</strong> diagrams, instructions and o<strong>the</strong>r similar in<strong>for</strong>mation,<br />
(n) connection <strong>of</strong> single pole devices <strong>for</strong> protection or switching in phase<br />
conductors only,<br />
(o) methods <strong>of</strong> fault protection,<br />
( p) prevention <strong>of</strong> mutual detrimental influence,<br />
(q) presence <strong>of</strong> undervoltage protective devices,<br />
(r) erection method.<br />
133