<strong>Code</strong> 21 PROCEDURES FOR INSPECTION,<br />

TESTING AND CERTIFICATION<br />

21A Inspection <strong>of</strong> Low Voltage Installations<br />

A visual inspection should be made to verify that <strong>the</strong> electrical equipment as<br />

installed is correctly selected and erected in accordance with <strong>the</strong> <strong>Wiring</strong><br />

<strong>Regulations</strong> and this CoP, and that <strong>the</strong>re is no apparent damage. The visual<br />

inspection should include a check on <strong>the</strong> following items, where appropriate:<br />

(a) adequacy <strong>of</strong> working space, access, and maintenance facilities,<br />

(b) connections <strong>of</strong> conductors,<br />

(c) identification <strong>of</strong> conductors,<br />

(d ) adequacy <strong>of</strong> <strong>the</strong> sizes <strong>of</strong> conductor in relation to current carrying capacity<br />

and voltage drop,<br />

(e) correct connections <strong>of</strong> all equipment with special attention to socket<br />

outlets, lampholders, isolators, switches, residual current devices,<br />

miniature circuit breakers, and protective conductors,<br />

(f ) presence <strong>of</strong> fire barriers and protection against <strong>the</strong>rmal effects,<br />

(g) methods <strong>of</strong> protection against direct contact with live parts (including<br />

measurement <strong>of</strong> distances where appropriate), i.e. protection by<br />

insulation <strong>of</strong> live parts, or protection by barriers or enclosures,<br />

(h) presence <strong>of</strong> appropriate devices <strong>for</strong> isolation and switching,<br />

(i) choice and setting <strong>of</strong> protective and indicative devices,<br />

( j) labelling <strong>of</strong> circuits, fuses, protective devices, switches, isolators and<br />

terminals,<br />

(k) selection <strong>of</strong> equipment and protective measures appropriate to adverse<br />

environmental conditions,<br />

(l) presence <strong>of</strong> danger and warning notices,<br />

(m) presence <strong>of</strong> diagrams, instructions and o<strong>the</strong>r similar in<strong>for</strong>mation,<br />

(n) connection <strong>of</strong> single pole devices <strong>for</strong> protection or switching in phase<br />

conductors only,<br />

(o) methods <strong>of</strong> fault protection,<br />

( p) prevention <strong>of</strong> mutual detrimental influence,<br />

(q) presence <strong>of</strong> undervoltage protective devices,<br />

(r) erection method.<br />