(d ) The spacing <strong>of</strong> <strong>the</strong> socket contacts should correspond with that <strong>of</strong> <strong>the</strong><br />
plug pins as shown in Figure A1(1).<br />
(e) On insertion <strong>of</strong> pins into contacts, <strong>the</strong> travel from <strong>the</strong> first point <strong>of</strong><br />
contact to <strong>the</strong> complete engagement, should not be less than <strong>the</strong><br />
minimum, or more than <strong>the</strong> maximum, given in Table A1(1).<br />
Table A1(1) Contact Travel<br />
Current Rating Minimum Maximum<br />
(ampere) (mm) (mm)<br />
5 4.17 6.25<br />
15 4.75 6.83<br />
(f ) Socket contacts should be self-adjusting as to contact making and each<br />
socket contact should be such as to make and maintain, in normal use,<br />
effective electrical and mechanical contact with <strong>the</strong> corresponding plug<br />
pins. The means <strong>for</strong> producing <strong>the</strong> contact pressure should be associated<br />
with each socket contact independently such that individual line or<br />
neutral socket contact should be capable <strong>of</strong> retaining <strong>the</strong> withdrawal—<br />
pull <strong>of</strong> a gauge as detailed in Figure A1(3) <strong>for</strong> 30 sec. when <strong>the</strong> socket<br />
outlet is held horizontally with <strong>the</strong> gauge hanging vertically downwards.<br />
It should be checked that nei<strong>the</strong>r shutter nor <strong>the</strong> cover/moulding has any<br />
effect on <strong>the</strong> results.<br />
(g) Where a shutter is provided, <strong>the</strong> construction <strong>of</strong> <strong>the</strong> socket outlet should<br />
be such that when a plug is withdrawn from it, <strong>the</strong> current carrying<br />
socket contacts are automatically screened by <strong>the</strong> shutter. The shutter<br />
should be operated by <strong>the</strong> insertion <strong>of</strong> <strong>the</strong> earthing pin.<br />
(h) (i) Unless a shutter is provided, diameter <strong>of</strong> holes in <strong>the</strong> socket outlet<br />
plate or cover <strong>for</strong> <strong>the</strong> reception <strong>of</strong> <strong>the</strong> line and <strong>the</strong> neutral plug pins<br />
should not exceed 5.8 mm or 7.7 mm <strong>for</strong> 5A or 15A socket outlet<br />
respectively.<br />
(ii) The holes <strong>for</strong> <strong>the</strong> line and <strong>the</strong> neutral plug pins in metal plates<br />
should have insulated material <strong>of</strong> at least 2 mm thick around <strong>the</strong>m.<br />
(i) The socket outlet should be constructed to prevent a current carrying pin<br />
<strong>of</strong> a plug from making contact with a current carrying contact <strong>of</strong> <strong>the</strong><br />
socket while ei<strong>the</strong>r or both <strong>of</strong> o<strong>the</strong>r pins are completely exposed. The<br />
provision <strong>of</strong> a shutter, or no part <strong>of</strong> hole intended <strong>for</strong> <strong>the</strong> reception <strong>of</strong><br />
line or neutral pin should be less than 16.5 mm or 21 mm from <strong>the</strong> edge<br />
<strong>of</strong> a 5A or 15A socket outlet respectively, is acceptable <strong>for</strong> this purpose.<br />
210