(2) Basic protection and fault protection<br />

Where protection by <strong>the</strong> use <strong>of</strong> SELV or functional extra low voltage<br />

(FELV) is used, <strong>the</strong> voltage should not exceed 25V a.c., r.m.s. or 60V<br />

ripple free d.c. and, regardless <strong>of</strong> <strong>the</strong> voltage, basic protection should be<br />

provided by:<br />

(a) a barrier or enclosure af<strong>for</strong>ding at least <strong>the</strong> degree <strong>of</strong> protection<br />

IP2X or IPXXB or equivalent, or<br />

(b) insulation capable <strong>of</strong> withstanding a test voltage <strong>of</strong> 500V d.c. <strong>for</strong> 60<br />

seconds.<br />

(3) Basic protection<br />

Protection by obstacles or placing out <strong>of</strong> reach is not permitted.<br />

(4) Fault protection<br />

(a) Fault protection should be provided by one <strong>of</strong> <strong>the</strong> following:<br />

(i) SELV,<br />

(ii) automatic disconnection, a supplementary equipotential<br />

bonding conductor should be provided and be connected to <strong>the</strong><br />

exposed conductive parts <strong>of</strong> <strong>the</strong> fixed equipment and <strong>the</strong><br />

conductive parts <strong>of</strong> <strong>the</strong> location,<br />

(iii) electrical separation, in which case only one socket or piece <strong>of</strong><br />

equipment should be connected to each secondary winding <strong>of</strong><br />

<strong>the</strong> isolating trans<strong>for</strong>mer, or<br />

(iv) <strong>the</strong> use <strong>of</strong> Class II equipment adequately protected to an IP<br />

code (see IEC 60529) in which case <strong>the</strong> circuit should be fur<strong>the</strong>r<br />

protected by a residual current device having <strong>the</strong> characteristics<br />

specified in <strong>Code</strong> 11J.<br />

(b) A supply to or a socket intended to supply a hand lamp should be<br />

protected by SELV.<br />

(c) If a functional earth is required <strong>for</strong> certain equipment, <strong>for</strong> example<br />

measurement or control apparatus, equipotential bonding should be<br />

provided between all exposed conductive parts, all extraneous<br />

conductive parts inside <strong>the</strong> restrictive conductive location, and <strong>the</strong><br />

functional earth.<br />

(d ) A supply to or a socket intended to supply a handheld tool should be<br />

protected by SELV or electrical separation.<br />

(e) A supply to fixed equipment should be protected by one <strong>of</strong> <strong>the</strong><br />

methods listed in subparagraph (a) above.<br />