Zone 2 is limited by:<br />

(a) <strong>the</strong> vertical plane external to Zone 1 and a parallel plane 1.5 m from<br />

<strong>the</strong> <strong>for</strong>mer,<br />

(b) <strong>the</strong> floor or surface expected to be occupied by persons, and<br />

(c) <strong>the</strong> horizontal plane 2.5 m above <strong>the</strong> floor or surface expected to be<br />

occupied by persons.<br />

There is no Zone 2 <strong>for</strong> fountains.<br />

(3) Bonding<br />

All extraneous conductive parts in Zones 0, 1 and 2 should be connected<br />

by supplementary equipotential bonding conductors to <strong>the</strong> protective<br />

conductors <strong>of</strong> exposed conductive parts <strong>of</strong> equipment situated in <strong>the</strong>se<br />

Zones.<br />

(4) Application <strong>of</strong> protective measures against electric shock<br />

(a) Except <strong>for</strong> fountains as stated in <strong>Code</strong> 26M(6), in Zone 0 only<br />

protection by SELV at a nominal voltage not exceeding 12V a.c.<br />

r.m.s. or 30V ripple-free d.c. is permitted, <strong>the</strong> source <strong>for</strong> SELV being<br />

installed outside Zones 0, 1 and 2.<br />

(b) Except <strong>for</strong> fountains as stated in <strong>Code</strong> 26M(6), in Zone 1 only<br />

protection by SELV at a nominal voltage not exceeding 25V a.c.<br />

r.m.s. or 60V ripple-free d.c. is permitted, <strong>the</strong> source <strong>for</strong> SELV being<br />

installed outside Zones 0, 1 and 2.<br />

(c) Equipment <strong>for</strong> use in <strong>the</strong> interior <strong>of</strong> basins which is only intended to<br />

be in operation when people are not inside Zone 0 should be<br />

supplied by a circuit protected by:<br />

• SELV, <strong>the</strong> source <strong>for</strong> SELV being installed outside Zones 0, 1 and<br />

2. However, it is permitted to install <strong>the</strong> source <strong>for</strong> SELV in<br />

Zone 2 if its supply circuit is protected by an RCD having <strong>the</strong><br />

characteristics specified in <strong>Code</strong> 11J, or<br />

• automatic disconnection <strong>of</strong> supply, using an RCD having <strong>the</strong><br />

characteristics specified in <strong>Code</strong> 11J, or<br />

• electrical separation, <strong>the</strong> source <strong>for</strong> electrical separation supplying<br />

only one item <strong>of</strong> current using equipment and being installed<br />

outside Zones 0, 1 and 2. However, it is permitted to install <strong>the</strong><br />

source in Zone 2 if its supply circuit is protected by an RCD having<br />

<strong>the</strong> characteristics specified in <strong>Code</strong> 11J.<br />

(d ) In Zone 2, one or more <strong>of</strong> <strong>the</strong> following protective measures should<br />

be employed:<br />

189