Appendix 1<br />

Prescribed Requirements <strong>for</strong> 3-pin (non-reversible)<br />

5 ampere and 15 ampere Socket Outlets<br />

(1) General<br />

A 5A or 15A socket outlet to BS 546 is acceptable as complying with <strong>the</strong><br />

prescribed requirements <strong>of</strong> this appendix.<br />

(2) Materials <strong>for</strong> plate/cover, base and current carrying<br />

parts<br />

(a) Parts made <strong>of</strong> ferrous metal should be rendered rust pro<strong>of</strong>, special<br />

attention being given to springs and moving parts.<br />

(b) (i) Insulating materials should be tough, non-ignitable and having a<br />

plastic yield not exceeding 6 mm when heated to a temperature <strong>of</strong><br />

100°C in accordance with <strong>the</strong> plastic yield test method 102A <strong>of</strong><br />

BS2782 Part 1 or equivalent.<br />

(ii) Current carrying parts, including earthing contact should be made <strong>of</strong><br />

brass, copper, phosphor-bronze, and/or o<strong>the</strong>r suitable material.<br />

(iii) A shutter if provided, <strong>the</strong> distortion <strong>of</strong> <strong>the</strong> material should not be<br />

such as to impede its action.<br />

(iv) The enclosure <strong>of</strong> <strong>the</strong> socket outlet should be rigid and be capable <strong>of</strong><br />

withstanding a minimum <strong>for</strong>ce <strong>of</strong> 4 kg applied over an area <strong>of</strong> 250<br />

mm2 anywhere on <strong>the</strong> surface without causing appreciable damage<br />

or reducing <strong>the</strong> protective clearance below <strong>the</strong> minimum values<br />

specified in paragraph (6).<br />

(3) Construction <strong>of</strong> socket outlet<br />

(a) (i) Socket outlets are to be constructed to accommodate <strong>the</strong> plug<br />

having physical dimensions as detailed in Figure A1(1).<br />

(ii) In this appendix, where reference is made to a plug, it means a plug<br />

having a corresponding rating and dimensions as detailed in Figure<br />

A1(1).<br />

(b) The configuration <strong>of</strong> <strong>the</strong> socket contacts should be as shown in Figure<br />

A1(2).<br />

(c) There should be no projection on <strong>the</strong> minimum engagement surface <strong>of</strong><br />

<strong>the</strong> socket outlet within a circle having <strong>the</strong> radius illustrated in Figure<br />

A1(2) and concentric with a circle through <strong>the</strong> centres <strong>of</strong> <strong>the</strong> contacts,<br />

such as would prevent <strong>the</strong> full insertion <strong>of</strong> a plug. Raised marking is<br />

permitted provided it does not project more than 0.5 mm from <strong>the</strong><br />

engagement surface.<br />

209