TABLE A6(8)<br />

Multicore armoured XLPE insulated cables<br />

(COPPER CONDUCTORS)<br />

BS 5467 Ambient temperature: 30°C<br />

CURRENT CARRYING CAPACITY (Amperes): BS 6724 Conductor operating temperature: 90°C<br />

Reference Method 11<br />

(on a per<strong>for</strong>ated horizontal or vertical cable tray), or<br />

Reference Method 13 (free air)<br />

Reference Method 1<br />

(clipped direct)<br />

Conductor crosssectional<br />

area<br />

1 three- or four-core cable,<br />

three-phase a.c.<br />

5<br />

1 two-core cable,<br />

single-phase a.c. or d.c.<br />

4<br />

1 three or four-core cable,<br />

three-phase a.c.<br />

3<br />

1 two-core cable,<br />

single-phase a.c. or d.c.<br />

2<br />

1<br />

A<br />

25<br />

33<br />

44<br />

56<br />

78<br />

99<br />

131<br />

162<br />

197<br />

251<br />

304<br />

353<br />

406<br />

463<br />

546<br />

628<br />

728<br />

A<br />

29<br />

39<br />

52<br />

66<br />

90<br />

115<br />

152<br />

188<br />

228<br />

291<br />

354<br />

410<br />

472<br />

539<br />

636<br />

732<br />

847<br />

A<br />

23<br />

31<br />

42<br />

53<br />

73<br />

94<br />

124<br />

154<br />

187<br />

238<br />

289<br />

335<br />

386<br />

441<br />

520<br />

599<br />

673<br />

A<br />

27<br />

36<br />

49<br />

62<br />

85<br />

110<br />

146<br />

180<br />

219<br />

279<br />

338<br />

392<br />

451<br />

515<br />

607<br />

698<br />

787<br />

mm2 1.5<br />

2.5<br />

4<br />

6<br />

10<br />

16<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

272<br />

NOTE: Refer Notes 1, 2 and 3 <strong>of</strong> table A6(5).