etween <strong>the</strong> base and <strong>the</strong> inside walls <strong>of</strong> <strong>the</strong> box or enclosure is not<br />

less than 6 mm.<br />

(ii) There should be no live metal protruding from or flush with <strong>the</strong><br />

socket outlet base. Any exposed live metal part should be recessed<br />

at least 2.5 mm from <strong>the</strong> base surface.<br />

(iii) Where it is intended that <strong>the</strong> fixed wiring conductors pass through<br />

holes in <strong>the</strong> base <strong>of</strong> <strong>the</strong> socket outlet to <strong>the</strong> terminals, <strong>the</strong> minimum<br />

diameter <strong>of</strong> each hole should not be less than 9.5 mm.<br />

(4) Construction <strong>of</strong> terminals<br />

(a) Line and neutral terminals in <strong>the</strong> socket outlet should permit <strong>the</strong><br />

connection, without special preparation, <strong>of</strong> one, two or three 2.5 mm2 solid or stranded or <strong>of</strong> one or two 4 mm2 stranded conductors.<br />

(b) Earthing terminals should permit <strong>the</strong> connection without special<br />

preparation, <strong>of</strong> one, two or three 1.5 mm2 or 2.5 mm2 solid or stranded<br />

or <strong>of</strong> one or two 4 mm2 stranded conductors.<br />

(c) Where pillar terminals are used <strong>the</strong>y should have clamping screws <strong>of</strong><br />

sufficient length to extend to <strong>the</strong> far side <strong>of</strong> <strong>the</strong> conductor hole. The end<br />

<strong>of</strong> <strong>the</strong> screw should be slightly rounded so as to minimize damage to <strong>the</strong><br />

conductors. The sizes <strong>of</strong> <strong>the</strong> conductor hole and <strong>the</strong> clamping screw<br />

should be such that <strong>the</strong> clearance between <strong>the</strong> sides <strong>of</strong> <strong>the</strong> major<br />

diameter <strong>of</strong> <strong>the</strong> clamping screw and <strong>the</strong> conductor hole does not exceed<br />

0.6 mm. The size <strong>of</strong> conductor hole should not be less than 4.3 mm.<br />

(d ) Terminal screws should have a nominal diameter <strong>of</strong> not less than 3 mm.<br />

(5) Screws and connections<br />

(a) Screwed connections, electrical and o<strong>the</strong>rwise should withstand <strong>the</strong><br />

mechanical stresses occurring in normal use. Screws transmitting<br />

electrical contact pressure should screw into metal.<br />

(b) Screws should not be <strong>of</strong> insulating material if <strong>the</strong>ir replacement by a<br />

metal screw would affect <strong>the</strong> safety or per<strong>for</strong>mance requirements <strong>of</strong> <strong>the</strong><br />

accessory.<br />

(c) Where current carrying parts are screwed toge<strong>the</strong>r, <strong>the</strong> current path<br />

should not rely on <strong>the</strong> screw threads.<br />

(6) Creepage distances, clearances and distances through<br />

insulation<br />

(a) When <strong>the</strong> socket outlet is correctly assembled and wired with <strong>the</strong><br />

appropriate cable, <strong>the</strong> minimum clearance through air and <strong>the</strong> minimum<br />

creepage distance shall be 2.5 mm:<br />

(i) between live parts <strong>of</strong> opposite polarity;<br />

219