(2) Correction factors <strong>for</strong> groups <strong>of</strong> cables<br />

Table A5(3)<br />

Correction factors <strong>for</strong> groups <strong>of</strong> more than one circuit <strong>of</strong><br />

single-core cables, or more than one multicore cable<br />

* ‘Spaced’ means a clearance between adjacent surfaces <strong>of</strong> at least one cable diameter (De).<br />

Where <strong>the</strong> horizontal clearances between adjacent cables exceeds 2De, no correction factor<br />

needs to be applied.<br />

# Not applicable to Mineral Insulated Cables. Please refer to BS 7671 <strong>for</strong> <strong>the</strong> required correction<br />

factors.<br />

Notes to Table A5(3)<br />

1. The factors in <strong>the</strong> table are applicable to groups <strong>of</strong> cables <strong>of</strong> one size<br />

only. The value <strong>of</strong> current derived from application <strong>of</strong> <strong>the</strong> appropriate<br />

factors is <strong>the</strong> maximum continuous current to be carried by any <strong>of</strong> <strong>the</strong><br />

cables in <strong>the</strong> group.<br />

2. If, due to known operating conditions, a cable is expected to carry not<br />

more than 30% <strong>of</strong> its grouped rating, it may be ignored <strong>for</strong> <strong>the</strong> purpose<br />

<strong>of</strong> obtaining <strong>the</strong> rating factor <strong>for</strong> <strong>the</strong> rest <strong>of</strong> <strong>the</strong> group.<br />

3. When cables having different conductor operating temperatures are<br />

grouped toge<strong>the</strong>r, <strong>the</strong> current rating should be based upon <strong>the</strong> lowest<br />

operating temperature <strong>of</strong> any cable in <strong>the</strong> group.<br />

253