Table 11(4)<br />

Minimum Cross-sectional Area <strong>of</strong> Protective Conductor <strong>for</strong><br />

Circuits Protected by HBC Fuses to BS1361<br />

Fuse Rating (Amp) 5 15 20 30 45 60 80 100<br />

Minimum cross-sectional<br />

area (sq. mm) <strong>of</strong><br />

Copper 1 1 1.5 2.5 4 10 10 16<br />

protective conductor <strong>for</strong><br />

5 sec. disconnection<br />

Aluminium 16 16 16 16 16 16 16 25<br />

Minimum cross-sectional<br />

area (sq. mm) <strong>of</strong><br />

protective conductor <strong>for</strong><br />

0.4 sec. disconnection<br />

0.2 0Zs 0.03<br />

0.13Zs0.2 0<br />

0.08Zs0.13<br />

0.05Zs0.08<br />

0.03Zs0.05<br />

0.02Zs0.03<br />

0.00Zs0.02<br />

Copper 1 1 1 1 2.5<br />

Table 11(5)<br />

Minimum Cross-sectional Area <strong>of</strong> Protective Conductor <strong>for</strong> Circuits Protected<br />

by Miniature Circuit Breaker Type 1 & 2 to BS 3871 or Equivalent<br />

Earth Fault Loop<br />

Impedance Zs (ohm)<br />

Minimum Cross-sectional Area <strong>of</strong> Protective Conductor (mm2 )<br />

<strong>for</strong> 5 Sec. and 0.4 Sec. Disconnection<br />

Copper Aluminium<br />

1 .000<br />

1.5 00<br />

2.5 00<br />

4.0 00<br />

6.0 00<br />

10 .00<br />

16 .00<br />

Table 11(6)<br />

Minimum Cross-sectional Area <strong>of</strong> Protective Conductor <strong>for</strong><br />

Circuit Protected by Miniature Circuit Breaker (MCB) Type 3,<br />

Type B & Type C to IEC 60898 or Equivalent<br />

MCB Rating (Amp) 05<br />

10 15 20 30 50 60 80 100<br />

Minimum cross-sectional<br />

area (sq. mm) <strong>of</strong><br />

Copper 01<br />

1.5 2.5 2.5 4 10 10 16 16<br />

protective conductor <strong>for</strong><br />

5 sec. disconnection<br />

Aluminium 16 16 16 16 16 16 16 16 25<br />

Minimum cross-sectional<br />

area (sq. mm) <strong>of</strong><br />

protective conductor <strong>for</strong><br />

0.4 sec. disconnection<br />

(Please refer to Table 11(5))<br />

80<br />

16<br />

16<br />

16<br />

16<br />

16<br />

16<br />

25