plug. The permanent connection to <strong>the</strong> fixed wiring may be by<br />
means <strong>of</strong> a flexible cable, or<br />
(ii) a monitoring system to BS4444 may be installed which, in <strong>the</strong> event<br />
<strong>of</strong> a discontinuity in <strong>the</strong> protective conductor, automatically<br />
disconnects <strong>the</strong> supply by a residual current device complying with<br />
relevant recognised standards and having <strong>the</strong> characteristic specified<br />
in <strong>Code</strong> 11J or an overcurrent protective device described in <strong>Code</strong> 9.<br />
(e) For a final circuit supplying a number <strong>of</strong> socket outlets in a location<br />
intended to accommodate several items <strong>of</strong> equipment, where it is known<br />
or is reasonably to be expected that <strong>the</strong> total earth leakage current in<br />
normal service will exceed 10 mA, <strong>the</strong> circuit should be provided with a<br />
high integrity protective connection complying with one or more <strong>of</strong> <strong>the</strong><br />
arrangements described in paragraph ( f )(i) to ( f )(vi) <strong>of</strong> this <strong>Code</strong>.<br />
Alternatively a ring circuit may be used to supply a number <strong>of</strong> single<br />
socket outlets. There should be no spur from <strong>the</strong> ring and <strong>the</strong> supply<br />
ends <strong>of</strong> <strong>the</strong> protective conductor ring should be separately connected at<br />
<strong>the</strong> distribution board. The minimum size <strong>of</strong> <strong>the</strong> ring protective earth<br />
conductor should be 1.5 mm 2 .<br />
(f ) The fixed wiring <strong>of</strong> every final circuit intended to supply an item <strong>of</strong><br />
stationary equipment having an earth leakage current exceeding 10 mA<br />
in normal service should be provided with a high integrity protective<br />
connection complying with one or more <strong>of</strong> <strong>the</strong> arrangements described<br />
below:<br />
(i) a single protective conductor with a cross-sectional area <strong>of</strong> not less<br />
than 10 mm 2 ;<br />
(ii) separate duplicated protective conductors, having independent<br />
connections complying with <strong>Code</strong> 25D, each having a cross-sectional<br />
area not less than 4 mm 2 ;<br />
(iii) duplicate protective conductors incorporated in a multicore cable<br />
toge<strong>the</strong>r with <strong>the</strong> live conductors <strong>of</strong> <strong>the</strong> circuit, provided that <strong>the</strong><br />
total cross-sectional area <strong>of</strong> all <strong>the</strong> conductors <strong>of</strong> <strong>the</strong> cable is not less<br />
than 10 mm 2 . One <strong>of</strong> <strong>the</strong> protective conductors may be <strong>for</strong>med by a<br />
metallic armour, sheath or braid incorporated in <strong>the</strong> construction <strong>of</strong><br />
<strong>the</strong> cable and complying with <strong>Code</strong> 11C;<br />
(iv) duplicate protective conductors <strong>for</strong>med by metal conduit, trunking<br />
or ducting complying with <strong>Code</strong> 11C, and by a conductor having a<br />
cross-sectional area not less than 2.5 mm 2 installed in <strong>the</strong> same<br />
enclosure and connected in parallel with it;<br />
(v) an earth monitoring device which, in <strong>the</strong> event <strong>of</strong> a discontinuity in<br />
<strong>the</strong> protective conductor, automatically disconnects <strong>the</strong> supply <strong>of</strong> <strong>the</strong><br />
equipment;<br />
(vi) connection <strong>of</strong> <strong>the</strong> equipment to <strong>the</strong> supply by means <strong>of</strong> a doublewound<br />
trans<strong>for</strong>mer or o<strong>the</strong>r unit in which <strong>the</strong> input and output<br />
196