(c) 4 mm 2 PVC insulated copper cables as supplementary bonding<br />

are used to bond <strong>the</strong> window frames intended to support<br />

air-conditioners.<br />

(B) Example in steps <strong>of</strong> sizing cable conductors as<br />

described in <strong>Code</strong> 13A(3)<br />

1. Assumed data<br />

An immersion electric water heater rated at 220V, 2 kW is to be installed<br />

using a 2-core-and-earth PVC-insulated and shea<strong>the</strong>d, non-armoured<br />

cable. The supply will be taken from an existing 15A spare way in a<br />

consumer’s unit containing semi-enclosed (rewirable) fuses to BS3036.<br />

The supply cable will run <strong>for</strong> much <strong>of</strong> its 14 m length in a ro<strong>of</strong> space<br />

which is <strong>the</strong>rmally insulated with glass fibre. The ro<strong>of</strong> space ambient<br />

temperature is expected to be 35°C in summer and, where leaving <strong>the</strong><br />

consumer’s unit, <strong>the</strong> cable will be bunched with seven o<strong>the</strong>r 2 core-andearth<br />

cables.<br />

2. Steps in sizing cable conductors<br />

(a) Design current <strong>of</strong> <strong>the</strong> circuit<br />

Rated power <strong>of</strong> <strong>the</strong> heater 2000<br />

= ———————————– = —— = 9.1A<br />

Supply voltage 220<br />

(b) A 15A semi-enclosed (rewirable) fuse to BS3036 is chosen as <strong>the</strong><br />

overcurrent protective device.<br />

(c) Current carrying capacity <strong>of</strong> <strong>the</strong> conductors is determined by<br />

applying <strong>the</strong> following correction factors to <strong>the</strong> current rating <strong>of</strong> <strong>the</strong><br />

overcurrent protective device (i.e. 15A):<br />

(i) Ambient temperature factor = 0.97<br />

(From Table A5(2) <strong>of</strong> Appendix 5, using conditions:<br />

Ambient temperature = 35°C<br />

Type <strong>of</strong> insulation = General purpose PVC)<br />

(ii) Grouping factor = 0.52<br />

(From Table A5(3) <strong>of</strong> Appendix 5, using conditions:<br />

Number <strong>of</strong> multicore cable = 8<br />

Reference Method <strong>of</strong> installation = Bunched and clipped<br />

direct to a non-metallic<br />

surface (Method 1), from<br />

Appendix 7)<br />

294