Length <strong>of</strong><br />

Busbars<br />

(metres)<br />

Table 9(3)<br />

Approximate Prospective Fault Current at<br />

Tap-<strong>of</strong>f Positions <strong>of</strong> Busbar Rising Mains Installation in<br />

kA (kilo-Amperes)<br />

Rating <strong>of</strong> Rising Mains<br />

200–300A 400–500A 600–800A 1000–2500A<br />

kA kA kA kA<br />

10 24 26 30 33<br />

13 22 25 30 33<br />

16 21 24 30 33<br />

19 20 23 28 33<br />

22 18 22 28 33<br />

25 18 22 28 33<br />

28 17 21 26 30<br />

31 16 20 26 30<br />

34 15 20 26 30<br />

37 15 19 26 30<br />

40 14 18 24 30<br />

43 13 18 24 30<br />

46 13 17 24 30<br />

49 12 17 24 30<br />

52 12 17 24 28<br />

55 11 16 24 28<br />

58 11 16 22 28<br />

61 11 15 22 28<br />

64 10 15 22 28<br />

67 10 15 22 28<br />

70 10 14 22 28<br />

73 9 14 22 28<br />

76 9 14 20 26<br />

79 9 13 20 26<br />

82 9 13 20 26<br />

85 8 13 20 26<br />

88 8 13 20 26<br />

91 8 12 20 26<br />

94 8 12 20 26<br />

97 7 12 20 26<br />

(Note: The in<strong>for</strong>mation and values given in this Table are intended <strong>for</strong><br />

general guidance only as <strong>the</strong> prospective fault current will vary <strong>for</strong><br />

different kinds <strong>of</strong> busbars)<br />

63