(d ) Where a residual current device is used, it should:<br />

(i) pass type test to IEC 61008 (<strong>for</strong> RCCB) or IEC 61009 (<strong>for</strong> RCBO)<br />

or equivalent;<br />

(ii) be suitable <strong>for</strong> independent toggle operation;<br />

(iii) have its tripping operation not dependent on a separate<br />

auxiliary supply; and<br />

(iv) have an integral test device on <strong>the</strong> front <strong>of</strong> every RCD to enable<br />

<strong>the</strong> automatic tripping operation to be tested by simulation <strong>of</strong><br />

an earth fault condition.<br />

(e) When two or more residual current devices are installed in series and<br />

where discrimination <strong>of</strong> <strong>the</strong>ir operation is necessary to prevent<br />

danger, <strong>the</strong> characteristics <strong>of</strong> <strong>the</strong> devices should be arranged to<br />

achieve <strong>the</strong> intended discrimination. In general, a time delay should<br />

be provided in <strong>the</strong> upstream device, <strong>for</strong> example, by <strong>the</strong> use <strong>of</strong> a<br />

“Type S” (or selective) device.<br />

11K Earth Electrodes<br />

Requirements <strong>for</strong> earth electrodes are described in <strong>Code</strong> 12.<br />

Table 11(1)<br />

Minimum Cross-sectional Area <strong>of</strong> Separate Protective Conductor<br />

Installation<br />

Method<br />

PVC Insulated (mm 2 ) Bare (mm 2 )<br />

Copper Aluminium Copper Aluminium<br />

Surface wiring 2.5 (shea<strong>the</strong>d) 16<br />

4.0 (non-shea<strong>the</strong>d)<br />

In Conduits or<br />

trunkings<br />

> 6 16<br />

1.0 16 1.0 16<br />