Table 5(2)<br />

Permissible Arrangements <strong>for</strong> Segregation <strong>of</strong><br />

Category 3 and Category 1 & 2 Circuits (With Enclosures)<br />

Method <strong>of</strong> Installation Conditions to be complied with<br />

Different conduits, ducts,<br />

ductings or trunkings<br />

Common channel or<br />

trunking<br />

(a)<br />

(b)<br />

—<br />

Cables <strong>of</strong> Category 3 circuits should be<br />

segregated from circuits <strong>of</strong> o<strong>the</strong>r<br />

categories by continuous partitions and<br />

<strong>the</strong>se partitions should also be provided at<br />

any common outlets OR<br />

Where mineral insulated cables or cables<br />

whose per<strong>for</strong>mance complies with BS<br />

6387 are used <strong>for</strong> Category 3 circuits,<br />

such a partition is not normally required<br />