(d ) Labels <strong>for</strong> identification purposes should preferably be written in<br />

both Chinese and English. Warning labels must be written in both<br />

Chinese and English.<br />

(2) Maintenance<br />

(a) In <strong>the</strong> design, construction and installation <strong>of</strong> an electrical<br />

installation, consideration must be given to its subsequent<br />

maintenance. It should be noted that electrical equipment must not<br />

only be so constructed and protected as to be suitable <strong>for</strong> <strong>the</strong><br />

conditions under which <strong>the</strong>y are required to operate, but must also<br />

be installed to be capable <strong>of</strong> being maintained, inspected and tested<br />

with due regard to safety.<br />

(b) For <strong>the</strong> purpose <strong>of</strong> maintenance, it is important to ensure <strong>the</strong> safety<br />

<strong>of</strong> persons approaching electrical equipment to work on it or attend<br />

to it. Guidelines on <strong>the</strong> provision <strong>of</strong> adequate and safe means <strong>of</strong><br />

access and working space are described in <strong>Code</strong>s 4E and 4F.<br />

(3) Inspection and testing<br />

(a) On completion <strong>of</strong> an installation or an extension <strong>of</strong> an installation,<br />

appropriate tests and inspection shall be made, to verify so far as is<br />

reasonably practicable that <strong>the</strong> requirements <strong>of</strong> <strong>the</strong> <strong>Wiring</strong><br />

<strong>Regulations</strong> have been met.<br />

(b) The power factor measured at consumer’s supply point <strong>of</strong> a<br />

consumer’s load should be maintained at a minimum <strong>of</strong> 0.85<br />

lagging and necessary power factor correction equipment should be<br />

installed.<br />

(c) An assessment should be made <strong>of</strong> any characteristics <strong>of</strong> equipment<br />

likely to have harmful effects upon o<strong>the</strong>r electrical equipment or<br />

o<strong>the</strong>r services, or impair <strong>the</strong> supply. Those characteristics include <strong>the</strong><br />

following:<br />

• overvoltages;<br />

• undervoltages;<br />

• fluctuating loads;<br />

• unbalanced loads;<br />

• power factor;<br />

• starting currents;<br />

• harmonic currents;<br />

• d.c. feedback;<br />

• high-frequency oscillations;<br />

• necessity <strong>for</strong> additional connection to earth.<br />

21