(a) <strong>the</strong> ambient temperature does not exceed 35°C;<br />

(b) no more than one circuit <strong>of</strong> single core cables or one multicore cable<br />

are to be grouped toge<strong>the</strong>r;<br />

(c) <strong>for</strong> cables clipped direct on surface, <strong>the</strong> spacing between groups <strong>of</strong><br />

single core cables or multicore cables is not less than twice <strong>the</strong><br />

diameter <strong>of</strong> <strong>the</strong> largest cable in <strong>the</strong> adjacent group <strong>of</strong> cables;<br />

(d ) <strong>the</strong> protective device is not a semi-enclosed fuse; and<br />

(e) <strong>the</strong> cables are not in contact with any <strong>the</strong>rmal insulation.<br />

13B Basic Protection<br />

(1) Protection by electrical insulation<br />

(a) Live conductors should be completely covered with insulation which:<br />

(i) is durably withstanding <strong>the</strong> mechanical, electrical, <strong>the</strong>rmal and<br />

chemical stresses to which it may be subjected in service; and<br />

(ii) can only be removed by destruction.<br />

(b) Where insulation is applied during <strong>the</strong> erection <strong>of</strong> <strong>the</strong> installation,<br />

<strong>the</strong> quality <strong>of</strong> <strong>the</strong> insulation should be verified by tests equivalent to<br />

those specified in recognised standards <strong>for</strong> similar type-tested<br />

equipment.<br />

(c) Non-impregnated paper, asbestos, fabric, wood or press-hemp<br />

should not be used <strong>for</strong> insulating purposes.<br />

(d ) Where insulating tapes are permitted to be used in low voltage<br />

installations, <strong>the</strong>y should have a minimum thickness <strong>of</strong> 0.21 mm.<br />

(2) Protection by o<strong>the</strong>r means<br />

O<strong>the</strong>r means <strong>of</strong> basic protection as stipulated in IEC 60364 or BS7671 are<br />

acceptable.<br />

13C Joints and Connections<br />

(a) Every connection at a cable termination or joint should:<br />

(i) be mechanically and electrically sound;<br />

(ii) be protected against moisture, mechanical damage and any<br />

vibration liable to occur;<br />

(iii) not impose any appreciable mechanical strain on <strong>the</strong> fixings <strong>of</strong> <strong>the</strong><br />

connection;<br />

(iv) not cause any harmful damage to <strong>the</strong> cable conductor;<br />

(v) be appropriate to <strong>the</strong> size and type <strong>of</strong> conductors with which <strong>the</strong>y<br />

are to be used; and<br />

91