Checklist No. 4—Additional Items For New L.V. Installation<br />

Installation Address: __________________________________________<br />

Tested by/Date<br />

(N/A if not applicable)<br />

(a) Switchboards,<br />

switches<br />

circuit breakers and main<br />

(i) Safe access and adequate clearance space<br />

provided.<br />

(ii) Number <strong>of</strong> source <strong>of</strong> supply: ______ and<br />

<strong>the</strong> rating <strong>of</strong> each <strong>of</strong> <strong>the</strong>m: _____________<br />

___________________<br />

_____________________________________ ___________________<br />

(iii) Maximum loading approved by <strong>the</strong><br />

electricity supplier: ____________________<br />

(iv) Suitable interlock scheme provided to<br />

prevent parallel operation <strong>of</strong> two or more<br />

sources <strong>of</strong> supply and 4-pole incoming and<br />

interconnecting circuit breakers provided<br />

<strong>for</strong> supply to be taken from more than one<br />

___________________<br />

source and is interconnected.<br />

(v) Electrically and mechanically interlocked<br />

4-pole changeover device(s) where standby<br />

___________________<br />

generator set(s) is installed.<br />

(vi) The breaking capacity <strong>of</strong> <strong>the</strong> main switch is<br />

______ kA and all circuit breakers/interconnection<br />

devices are able to withstand<br />

___________________<br />

<strong>the</strong> prospective fault current.<br />

(vii) Protective relays have been correctly set<br />

and overcurrent protective devices suitably<br />

___________________<br />

set <strong>for</strong> all circuits.<br />

(viii) Protective type C.T. are used <strong>for</strong> protective<br />

___________________<br />

relays.<br />

(ix) A means <strong>of</strong> isolation provided <strong>for</strong> every<br />

___________________<br />

circuit.<br />

(x) Operation <strong>of</strong> circuit breakers and main<br />

___________________<br />

switches checked.<br />

(xi) Control, indication and alarm functions<br />

___________________<br />

checked.<br />

(xii) No undersized conductor used between <strong>the</strong><br />

___________________<br />

main busbar and fuse/MCB’s.<br />

(xiii) Fuses/MCB’s matching <strong>the</strong> lowest rated<br />

___________________<br />

conductor in <strong>the</strong> circuit.<br />

___________________<br />

303