• SELV, <strong>the</strong> source <strong>of</strong> SELV being installed outside Zones 0, 1<br />
and 2. However, it is permitted to install <strong>the</strong> source <strong>of</strong> SELV<br />
in Zone 2 if its supply circuit is protected by a RCD having <strong>the</strong><br />
characteristics specified in <strong>Code</strong> 11J;<br />
• Automatic disconnection <strong>of</strong> supply, using an RCD having <strong>the</strong><br />
characteristics specified in <strong>Code</strong> 11J;<br />
• Electrical separation, <strong>the</strong> source <strong>for</strong> electrical separation<br />
supplying only one item <strong>of</strong> current using equipment, or one<br />
socket outlet, and being installed outside Zones 0, 1 and 2.<br />
However, it is permitted to install <strong>the</strong> source in Zone 2 if its<br />
supply circuit is protected by an RCD having <strong>the</strong><br />
characteristics specified in <strong>Code</strong> 11J.<br />
(iv) For a swimming pool where it is not possible to locate a socket<br />
outlet or switch outside Zone 1, a socket outlet or switch,<br />
preferably having a non-conductive cover or coverplate, is<br />
permitted in Zone 1 if it is installed outside (1.25 m) from <strong>the</strong><br />
border <strong>of</strong> Zone 0, is placed at least 0.3 m above <strong>the</strong> floor, and<br />
is protected by:<br />
• SELV, at a nominal voltage not exceeding 25V a.c. r.m.s. or<br />
60V ripple-free d.c., <strong>the</strong> source <strong>for</strong> SELV being installed<br />
outside Zones 0 and 1, or<br />
• automatic disconnection <strong>of</strong> supply, using an RCD having <strong>the</strong><br />
characteristics specified in <strong>Code</strong> 11J, or<br />
• electrical separation <strong>for</strong> a supply to only one item <strong>of</strong> current<br />
using equipment, <strong>the</strong> source <strong>for</strong> electrical separation being<br />
installed outside Zones 0 and 1.<br />
(d ) O<strong>the</strong>r equipment<br />
(i) In Zones 0 and 1, it is only permitted to install fixed current<br />
using equipment specifically designed <strong>for</strong> use in a swimming<br />
pool.<br />
(ii) Equipment which is intended to be in operation only when<br />
people are outside Zone 0 may be used in all zones provided<br />
that it is supplied by a circuit protected according to<br />
subparagraph (4) above.<br />
(iii) It is permitted to install an electric heating unit embedded in <strong>the</strong><br />
floor, provided that it:<br />
• is protected by SELV, <strong>the</strong> source <strong>of</strong> SELV being installed<br />
outside Zones 0, 1 and 2. However, it is permitted to install<br />
<strong>the</strong> source <strong>of</strong> SELV in Zone 2 if its supply circuit is protected<br />
by an RCD having <strong>the</strong> characteristics specified in <strong>Code</strong> 11J, or<br />
• incorporates an ear<strong>the</strong>d metallic sheath connected to <strong>the</strong><br />
supplementary equipotential bonding specified in<br />
subparagraph (3) above and its supply circuit is additionally<br />