(b) Subject to subparagraph (a) above, <strong>the</strong> cross-sectional area <strong>of</strong> a<br />

protective conductor, o<strong>the</strong>r than an equipotential or supplementary<br />

bonding conductor and not <strong>for</strong>ming part <strong>of</strong> a twin or multicore<br />

cable, that are selected in accordance with <strong>the</strong> appropriate Tables<br />

11(2), 11(3), 11(4), 11(5), 11(6) and 11(7) are considered acceptable.<br />

Alternatively, <strong>the</strong> cross-sectional area <strong>of</strong> <strong>the</strong> protective conductor<br />

can be calculated using <strong>the</strong> <strong>for</strong>mula given in regulation 543.1.3 <strong>of</strong><br />

BS 7671.<br />

(c) For an earthing conductor, requirements as stipulated in <strong>Code</strong> 11H<br />

also apply.<br />

(d ) Requirements <strong>for</strong> <strong>the</strong> cross-sectional areas <strong>of</strong> equipotential bonding<br />

conductors and supplementary bonding conductors are described in<br />

<strong>Code</strong>s 11E and 11F respectively.<br />

(e) Where metallic enclosures <strong>for</strong> cables, busbar trunking and<br />

switchgear and controlgear assemblies are used as protective<br />

conductors, <strong>the</strong>y should have cross-sectional area equivalent to that<br />

<strong>of</strong> copper, not less than that resulting from application <strong>of</strong> <strong>the</strong><br />

<strong>for</strong>mula given in regulation 543.1.3 <strong>of</strong> BS 7671, or in accordance<br />

with Table 11(2).<br />

11D Earthing <strong>of</strong> Exposed Conductive Parts<br />

(1) General<br />

Unless o<strong>the</strong>r effective precautions are taken to prevent danger, such as<br />

<strong>the</strong> use <strong>of</strong> double insulated equipment or <strong>the</strong> use <strong>of</strong> isolating trans<strong>for</strong>mer<br />

to BSEN 61558 or equivalent, all exposed conductive parts <strong>of</strong> equipment<br />

(o<strong>the</strong>r than live parts) should be connected by means <strong>of</strong> circuit protective<br />

conductors (CPC) to <strong>the</strong> main earthing terminal <strong>of</strong> <strong>the</strong> installation and<br />

<strong>the</strong> terminal should be connected to earth electrode(s) via earthing<br />

conductor(s).<br />

(2) Types <strong>of</strong> exposed conductive parts<br />

(a) Exposed conductive parts include:<br />

(i) metallic enclosure <strong>of</strong> current using equipment, o<strong>the</strong>r than<br />

double insulated equipment;<br />

(ii) metallic conduit, trunking and ducting <strong>for</strong> enclosure <strong>of</strong> cable(s);<br />

(iii) metallic enclosures <strong>of</strong> current distribution equipment such as<br />

switchgear and controlgear assemblies.<br />

(b) Exposed conductive parts do not include:<br />

(i) wall brackets and metal parts connected to overhead line<br />

insulators if such parts are not readily accessible;<br />

(ii) inaccessible steel rein<strong>for</strong>cement in steel rein<strong>for</strong>ced concrete<br />

poles;<br />

70