TABLE A6(2)<br />

Multicore PVC insulated cables, non-armoured<br />

(COPPER CONDUCTORS)<br />

BS 6004 Ambient temperature: 30°C<br />

CURRENT CARRYING CAPACITY (Amperes): BS 6346 Conductor operating temperature: 70°C<br />

BS 7629<br />

260<br />

NOTE: 1. Where <strong>the</strong> conductor is to be protected by a semi-enclosed fuse to BS 3036, see Appendix 5(4).<br />

*2. With or without protective conductor.<br />

3. Circular conductors are assumed <strong>for</strong> sizes up to and including 16 mm2 . Values <strong>for</strong> larger sizes relate to shaped conductors and may safely be applied to<br />

circular conductors.<br />

4. Cables to BS 7629 are rated <strong>for</strong> a conductor operating temperature <strong>of</strong> 70°C and are <strong>the</strong>re<strong>for</strong>e included in this table, although <strong>the</strong> material used <strong>for</strong> <strong>the</strong><br />

cable insulation is not PVC.