Anderson Engineers, P.A.<br />

12041 – <strong>ROSEMARY</strong> <strong>BEACH</strong> OWNER’S CENTER<br />

SECTION 042000 - CONCRETE MASONRY<br />

PART 1 - GENERAL<br />

1.01 RELATED DOCUMENTS<br />

A. Conform to Division 1, Section 04000 and other sections of this division.<br />

1.02 APPLICABLE CODES AND STANDARDS<br />

A. Florida Building Code - latest edition adopted in building area.<br />

Building Code Requirements for Masonry Structures (ACI 530-05 / ASCE 5-99 / TMS 402-99).<br />

Specification for Masonry Structures (ACI 530-02 / ASCE 6-99 / TMS 602-99).<br />

PART 2 - PRODUCTS<br />

2.01 MORTAR MATERIALS<br />

A. Refer to Section 04000/Masonry, General.<br />

2.02 STEEL REINFORCEMENT<br />

A. Refer to Section 04000/Masonry, General.<br />

2.03 MASONRY WALL CLEANERS<br />

A. Refer to Section 04000/Masonry, General.<br />

2.04 MASONRY WALL CONTROL EXPANSION JOINTS<br />

A. Refer to Section 04000/Masonry, General.<br />

2.05 CONCRETE MASONRY UNITS<br />

A. STANDARD WEIGHT CONCRETE MASONRY UNITS<br />

1. Conform to ASTM C90-01a, grade "N", Type II, 8" x 16" and 12” x 16” modular units, thickness<br />

as indicated on the drawings, minimum 1" face shells. Units 8" or more thick must have<br />

minimum 1 1/4" face shells. Aggregate is to be gravel, air-cooled blast furnace slag, or crushed<br />

stone. Units are to be acceptable visually, structurally, and free from undesirable defects<br />

resulting from either manufacturer or handling, as judged by ARCHITECT.<br />

The design compressive strength of the masonry, f'm = 1500 psi minimum (1900 PSI on net<br />

area).<br />

2. Units which have not been subjected to an approved method of steam curing must be stored for<br />

30 days prior to use.<br />

3. Sound transmission loss through 4" unpainted unplastered wall, must not measure less than<br />

36 decibels.<br />

4. Linear drying shrinkage must not be greater than 0.04% when tested as prescribed by National<br />

Bureau of Standards.<br />

5. Moisture content at time of delivery must not exceed 75% of relative humidity, as measured by<br />

approved methods of Portland Cement Association.<br />

6. Standard brick sized units are to be solid, but otherwise conform to these paragraphs.<br />

B. ACCESSORY UNITS<br />

1. 8" x 16" x 8" thick header block at locations indicated.<br />

2. 8" x 16" knock out cut-lintel units, thickness as indicated.<br />

CONCRETE MASONRY 042000-1