DAG Architects Inc.<br />

12041 Rosemary Beach Owners Center<br />

Rosemary Beach, Fl.<br />

B. Accessories: Provide components for each through-penetration firestop system that<br />

are needed to install fill materials and to comply with Part 1 "Performance<br />

Requirements" Article. Use only components specified by through-penetration firestop<br />

system manufacturer and approved by qualified testing and inspecting agency for<br />

firestop systems indicated.<br />

2.3 SLEEVES FOR RACEWAYS AND CABLES<br />

A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized<br />

steel, plain ends.<br />

B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron<br />

pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.<br />

C. Coordinate sleeve selection and application with selection and application of<br />

firestopping.<br />

2.4 SLEEVE SEALS<br />

A. Description: Modular sealing device, designed for field assembly, to fill annular space<br />

between sleeve and raceway or cable.<br />

1. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or<br />

conduit. Include type and number required for material and size of raceway or<br />

cable.<br />

2. Pressure Plates: Plastic. Include two for each sealing element.<br />

3. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of<br />

length required to secure pressure plates to sealing elements. Include one for<br />

each sealing element.<br />

PART 3 - EXECUTION<br />

3.1 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLATION<br />

A. General: Install through-penetration firestop systems to comply with Part 1<br />

"Performance Requirements" Article and with firestop system manufacturer's written<br />

installation instructions and published drawings for products and applications indicated.<br />

B. Install forming/damming/backing materials and other accessories of types required to<br />

support fill materials during their application and in the position needed to produce<br />

cross-sectional shapes and depths required to achieve fire ratings indicated.<br />

1. After installing fill materials and allowing them to fully cure, remove combustible<br />

forming materials and other accessories not indicated as permanent components<br />

of firestop systems.<br />

C. Install fill materials for firestop systems by proven techniques to produce the following<br />

results:<br />