DAG Architects Inc.<br />

12041 Rosemary Beach Owners Center<br />

Rosemary Beach Fl.<br />

3.4.1 In addition to the data required for any specified performance tests, measure and record the<br />

temperatures, pressures, flow rates, and nameplate data for all components listed herein.<br />

3.4.2 It is the intent of this section to record data on balanced systems, under normal operating or<br />

design conditions.<br />

3.4.3 Temperatures:<br />

3.4.4 Pressures:<br />

1. Outside dry and wet bulb temperatures.<br />

2. Dry bulb temperature in each room and at least one wet bulb temperature in each zone.<br />

3. Refrigerant liquid and suction temperatures.<br />

4. Inlet and outlet temperature of each heat exchange device - both fluids.<br />

1. Suction and discharge static pressure of each fan.<br />

2. Suction and discharge pressure of each pump.<br />

3. Each refrigerant suction and discharge pressure.<br />

3.4.5 Flow rates:<br />

1. Flow rate through each fan.<br />

3.4.6 Nameplate Data:<br />

1. Complete nameplate data for all equipment.<br />

2. Motor data to include horsepower, phase, voltage, RPM, full load nameplate current, fuse<br />

rating in disconnect switch, number or manufacturer's size designation, and ampere<br />

rating of overcurrent and low voltage protection devices in starters.<br />

3.5 All test openings in ductwork shall be resealed in an approved manner.<br />

END OF SECTION 23 05 93<br />

TESTING AND BALANCING OF MECHANICAL SYSTEMS 23 05 93 - 4/4