3.2.1 Insulate round elbows and fittings with wrap such that thickness is equal to adjoining duct<br />

covering. Clean and dry ductwork prior to insulating.<br />

3.2.2 Adhere insulation to duct with 50 percent coverage using approved insulation adhesive applied<br />

in 6-inch wide swaths with 6-inch spaces between swaths. Additionally secure insulation with<br />

perforated pins and Tuff-Bond or by self-sticking pins with a 3/8" self-tapping screw. Space on<br />

12-inch centers and 3 inches from all edges. Ducts up through 24" wide only require one row<br />

of pins. Ducts over 24" wide shall have pins spaced as described herein.<br />

3.2.3 Lap all joints 2 inches and seal joints with 4-inch wide strips of open mesh glass fabric<br />

embedded in two coats of general purpose mastic.<br />

3.2.4 Seal all punctures and breaks in aluminum vapor barrier with open mesh glass fabric and<br />

vapor barrier sealant.<br />

END OF SECTION 23 07 13<br />

EXTERIOR INSULATION FOR DUCTWORK 23 07 13-2/2