DAG Architects Inc.<br />

12041 Rosemary Beach Owners Center<br />

Rosemary Beach Fl.<br />

2.6.1 Pipes:<br />

2.6.1.1 PVC DWV Pipe: ASTM D-2665, Schedule 40.<br />

2.6.1.2 PVC Sewer Pipe: ASTM D-3034.<br />

2.6.1.3 PVC Pressure Pipe: ASTM D-1785, Schedule 40 or 80.<br />

2.6.2 Fittings:<br />

2.6.2.1 PVC Solvent Cement: ASTM D-2564.<br />

2.6.2.2 PVC DWV Socket: ASTM D-2665.<br />

2.6.2.3 PVC Sewer Socket: ASTM D-3034.<br />

2.6.2.4 PVC Schedule 40 Socket: ASTM D-2466.<br />

2.6.2.5 PVC Schedule 80 Socket: ASTM D-2467.<br />

2.6.2.6 PVC Schedule 80 Threaded: ASTM D-2464.<br />

3 EXECUTION<br />

3.1 Installation<br />

3.1.1 General: Install pipes and pipe fittings in accordance with recognized industry practices which<br />

will achieve permanently-leak proof piping systems, capable of performing each indicated<br />

service without piping failure. Install each run with minimum joints and couplings, but with<br />

adequate and accessible unions for disassembly and maintenance or replacement of valves<br />

and equipment. Reduce sizes (where indicated) by use of reducing fittings, not bushings.<br />

Align piping accurately at connections, within 1/16" misalignment tolerance.<br />

3.1.2 Comply with ANSI B31 Code for Pressure Piping.<br />

3.1.3 Locate piping runs, except as otherwise indicated, vertically and horizontally (pitched to drain)<br />

and avoid diagonal runs wherever possible. Orient horizontal runs parallel with walls and<br />

column lines. Locate runs as shown or described by diagrams, details and notations or, if not<br />

otherwise indicated, run piping in shortest route which does not obstruct usable space or block<br />

access for servicing building and its equipment. Hold piping close to walls, overhead<br />

construction, columns and other structural and permanent-enclosure elements of building; limit<br />

clearance to ½" where furring is shown for enclosure or concealment of piping, but allow for<br />

insulation thickness, if any. Where possible, locate insulated piping for 1" clearance outside<br />

insulation.<br />

3.1.4 Concealed Piping: Unless specifically noted as “Exposed” on the drawings, conceal piping<br />

from view in finished and occupied spaces, by locating in column enclosures, chases, in hollow<br />

wall construction or above suspended ceilings; do not encase horizontal runs in solid<br />

partitions, except as indicated.<br />

3.1.5 Electrical Equipment Spaces: Do not run piping through transformer vaults and other<br />

electrical, communications, or data equipment spaces and enclosures unless shown. Install<br />

drip pan under piping that must run through electrical spaces.<br />

PIPES AND PIPE FITTINGS 22 11 16 - 3/6