DAG Architects Inc.<br />

12041 Rosemary Beach Owners Center<br />

Rosemary Beach Fl.<br />

SECTION 23 81 46 - WATER-TO-AIR HEAT PUMPS<br />

1 GENERAL<br />

1.1 Drawings and general provisions of Contract, including General and Supplementary Conditions<br />

and Division-1 Specification sections, apply to work of this section.<br />

1.2 Division 23 Basic Mechanical Materials and Methods sections apply to work of this section.<br />

1.3 Extent of water-to-air heat pump work required by this section is indicated on drawings and<br />

schedules, and by requirements of this section.<br />

1.4 Refer to Division 26 sections for electrical; not work of this section.<br />

1.5 Refer to other Division 23 sections for testing, adjusting, and balancing of air conditioning<br />

units; not work of this section.<br />

1.6 Approval Submittals:<br />

1.6.1 Product Data: Submit manufacturer's technical product data, including dimensions, ratings,<br />

electrical characteristics, weight, capacities, materials of construction, and installation<br />

instructions. Submit manufacturer's assembly-type drawings showing all piping and electrical<br />

connections and all mounting requirements. Show methods of fastening and assembly of<br />

components. Provide wiring diagrams.<br />

Water-to-air heat pump unit<br />

Vibration control<br />

Geothermal Loopfield Calculations and Piping<br />

1.6.2 O&M Data Submittals: Submit manufacturer's maintenance data including parts lists. Include<br />

these data, product data, and a copy of approval submittals in O&M manual.<br />

2 PRODUCTS<br />

2.1 Quality Assurance:<br />

2.1.1 Test and rate units in accordance with ARI Standard 240 and provide certified rating seal.<br />

2.1.2 Construct refrigeration system in accordance with ASHRAE 15 (ANSI B 9.1) "Safety Code for<br />

Mechanical Refrigeration".<br />

2.1.3 Provide units that are designed, manufactured, tested, and listed in accordance with UL<br />

requirements.<br />

2.1.4 Provide units with an SEER that meet the requirements of the Florida Energy Efficiency Code<br />

and the schedules on the drawings.<br />

2.1.5 Acceptable Manufacturers: Subject to compliance with requirements, provide units by<br />

Addison, Florida Heat Pump, Water Furnace, or approved equal.<br />

2.2 GENERAL ½ TO 6 TON UNITS: Units shall be performance certified to ISO standard 13256-1<br />

for Water Loop Heat Pump, Ground Water Heat Pump and Ground Loop Heat Pump<br />

applications. Units intended for use on ground loop applications shall have an optional<br />

extended range package installed. Units shall be Underwriter Laboratories (UL and cUL) listed<br />

for safety on all models. Each unit shall be run tested at the factory. Each unit shall be pallet<br />

mounted and stretch wrapped. The units shall be manufactured in an ISO9001:2000 certified<br />

WATER-TO-AIR HEAT PUMPS 23 81 46 - 1/4